Johnson Controls PC090 THRU 240 Manual Do Utilizador

Página de 33
430645-YIM-D-0610
Johnson Controls Unitary Products
9
Electrical Data
Table 5:
Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet
Model
Compressors
Outdoor Fan Motor
Pwr Conv Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty
RLA
(each)
MCC 
(each)
LRA
(each)
Power
Supply
HP
Qty
FLA
(each)
FLA
PC090
208/230-3-60
1
25.0
39
164
208/230-1-60
 1/3
2
2.1
-
35.5
45
460-3-60
1
12.2
19
100
460-1-60
 1/3
2
1.2
-
17.6
25
575-3-60
1
9.0
14
78
575-1-60
 1/3
2
0.9
-
13.1
20
PC120
208/230-3-60
2
18.1
28.3
137
208/230-1-60
 3/4
2
3.0
-
46.8
60
460-3-60
2
9.0
14.0
62
460-1-60
 3/4
2
1.6
-
23.5
30
575-3-60
2
6.8
10.6
50
575-1-60
 3/4
2
1.4
-
18.0
20
PC180
208/230-3-60
2
25.0
39
164
208/230-1-60
 1/3
4
2.1
-
64.7
80
460-3-60
2
12.2
19
100
460-1-60
 1/3
4
1.2
-
32.2
40
575-3-60
2
9.0
14
78
575-1-60
 1/3
4
0.9
-
24.0
30
PD180
208/230-3-60
2
25.0
39
164
208/230-1-60
 1/3
4
2.1
-
64.7
80
460-3-60
2
12.2
19
100
460-1-60
 1/3
4
1.2
-
32.2
40
575-3-60
2
9.0
14
78
575-1-60
 1/3
4
0.9
-
24.0
30
PC240
208/230-3-60
2
30.1
47
225
208/230-1-60
 3/4
4
3.0
-
79.8
100
460-3-60
2
16.7
26
114
460-1-60
 3/4
4
1.6
-
44.0
60
575-3-60
2
12.2
19
80
575-1-60
 3/4
4
1.4
-
32.9
45
PD240
208/230-3-60
2
30.1
47
225
208/230-1-60
 3/4
4
3.0
-
79.8
100
460-3-60
2
16.7
26
114
460-1-60
 3/4
4
1.6
-
44.0
60
575-3-60
2
12.2
19
80
575-1-60
 3/4
4
1.4
-
32.9
45
1.
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
Table 6:
Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet
Model
Compressors
Outdoor Fan Motor
Pwr Conv Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty
RLA
(each)
MCC 
(each)
LRA
(each)
Power
Supply
HP
Qty
FLA
(each)
FLA
PC090
208/230-3-60
1
25.0
39
164
208/230-1-60
 1/3
2
2.1
10.0
45.5
60
460-3-60
1
12.2
19
100
460-1-60
 1/3
2
1.2
5.0
22.6
30
575-3-60
1
9.0
14
78
575-1-60
 1/3
2
0.9
4.0
17.1
25
PC120
208/230-3-60
2
18.1
28.3
137
208/230-1-60
 3/4
2
3.0
10.0
56.8
70
460-3-60
2
9.0
14.0
62
460-1-60
 3/4
2
1.6
5.0
28.5
35
575-3-60
2
6.8
10.6
50
575-1-60
 3/4
2
1.4
4.0
22.0
25
PC180
208/230-3-60
2
25.0
39
164
208/230-1-60
 1/3
4
2.1
10.0
74.7
90
460-3-60
2
12.2
19
100
460-1-60
 1/3
4
1.2
5.0
37.2
45
575-3-60
2
9.0
14
78
575-1-60
 1/3
4
0.9
4.0
28.0
35
PD180
208/230-3-60
2
25.0
39
164
208/230-1-60
 1/3
4
2.1
10.0
74.7
90
460-3-60
2
12.2
19
100
460-1-60
 1/3
4
1.2
5.0
37.2
45
575-3-60
2
9.0
14
78
575-1-60
 1/3
4
0.9
4.0
28.0
35
PC240
208/230-3-60
2
30.1
47
225
208/230-1-60
 3/4
4
3.0
10.0
89.8
110
460-3-60
2
16.7
26
114
460-1-60
 3/4
4
1.6
5.0
49.0
60
575-3-60
2
12.2
19
80
575-1-60
 3/4
4
1.4
4.0
36.9
45
PD240
208/230-3-60
2
30.1
47
225
208/230-1-60
 3/4
4
3.0
10.0
89.8
110
460-3-60
2
16.7
26
114
460-1-60
 3/4
4
1.6
5.0
49.0
60
575-3-60
2
12.2
19
80
575-1-60
 3/4
4
1.4
4.0
36.9
45
1.
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.