Sanyo UHX3652 Manual Do Utilizador

Página de 114
6-3
Service Checker
1
2
3
4
5
6
7
8
LED
1. Outdoor Unit Maintenance Remote Controller
■  
Temperature monitor
     Displays the temperature from each indoor/outdoor sensor. 
■  
Outdoor unit alarm history monitor
     Displays the outdoor unit alarm history.
■  
Setting the outdoor unit EEPROM data
     Settings mode 1 and settings mode 2 can be used to make outdoor unit EEPROM data settings.
3. Ordinary Display Controls and Functions
■  
Functions on the ordinary display  
  
Connect the special service checker wiring to the outdoor unit PCB.
The connection diagram is shown below.
Fig. 6-1
Fig. 6-2
  If the inter-unit control wiring 
is connected, it can be left 
as-is.
  In the case of an independent 
outdoor unit (1 maintenance 
remote controller connected 
to 1 outdoor unit, automatic 
address setting for indoor 
units not completed), both 
setting mode 1 and setting 
mode 2 can be used for 
outdoor unit EEPROM data 
settings.
  The overall system status for 
that refrigerant system is 
displayed.
All units start/stop (Fig. 6-1)
<Operation>
The 
 (ON/OFF operation) button can be used to start and stop all 
indoor units.
• The LED illuminates if any indoor unit is operating.
• The LED blinks if an alarm occurs at any of the operating indoor units.
Cooling/heating change (Fig. 6-1)
<Operation>
The 
 (MODE) button can be used to change between heating and 
cooling operation.
• The display indicates the operating mode of the indoor unit with the lowest 
unit No.
All units test run (Fig. 6-2)
<Operation>
The 
 (CHECK) button can be used to start and stop a test run for all 
units. 
(To start, press and hold the button for 4 seconds.)
During the test run, “Test” is displayed.
• The status of test runs performed from the indoor unit remote controller is 
not displayed on the outdoor unit maintenance remote controller.
Special service checker wiring
Outdoor unit maintenance remote controller
Relay connector (2P, white)
PCB connector (3P, blue)
RC (3P, blue)
Outdoor unit PCB