Sanyo XHX1852 Manual Do Utilizador

Página de 114
ii
2.  The standards for minimum room volume are as fol-
lows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent 
room for ventilation of leaking refrigerant gas (open-
ing without a door, or an opening 0.15% or larger 
than the respective floor spaces at the top or bottom 
of the door).
(3) If an indoor unit is installed in each partitioned room 
and the refrigerant tubing is interconnected, the 
smallest room of course becomes the object. But 
when mechanical ventilation is installed interlocked 
with a gas leakage detector in the smallest room 
where the density limit is exceeded, the volume of the 
next smallest room becomes the object.
3.  The minimum indoor floor space compared with the 
amount of refrigerant is roughly as follows: (When the 
ceiling is 8.8 ft. high)
Check of Density Limit
The room in which the air conditioner is to be 
installed requires a design that in the event of refrig-
erant gas leaking out, its density will not exceed a set 
limit.
The refrigerant (R410A), which is used in the air con-
ditioner, is safe, without the toxicity or combustibility of 
ammonia, and is not restricted by laws imposed to protect 
the ozone layer. However, since it contains more than air, 
it poses the risk of suffocation if its density should rise 
excessively. Suffocation from leakage of refrigerant is 
almost non-existent. With the recent increase in the num-
ber of high density buildings, however, the installation of 
multi air conditioner systems is on the increase because of 
the need for effective use of floor space, individual control, 
energy conservation by curtailing heat and carrying power, 
etc.
Most importantly, the multi air conditioner system is able 
to replenish a large amount of refrigerant compared to 
conventional individual air conditioners. If a single unit 
of the multi air conditioner system is to be installed in a 
small room, select a suitable model and installation pro-
cedure so that if the refrigerant accidentally leaks out, 
its density does not reach the limit (and in the event of 
an emergency, measures can be made before injury can 
occur).
In a room where the density may exceed the limit, create 
an opening with adjacent rooms, or install mechanical 
ventilation combined with a gas leak detection device. 
The density is as given below.
Total amount of refrigerant (lbs)
Min. volume of the indoor unit installed room (ft.
3
)
 
< Density limit (oz/ft.
3
)
The density limit of refrigerant which is used in multi air 
conditioners is 0.3 oz/ft.
3
 (ISO 5149).
NOTE
1.If there are 2 or more refrigerating systems in a single 
refrigerating device, the amount of refrigerant should be 
as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in 
rooms A, B and C is 353 oz.
The possible amount of leaked refrigerant gas in 
rooms D, E and F is 529 oz.
Outdoor unit 
Refrigerant tubing 
Indoor unit
e.g., charged  
amount (353 oz) 
Outdoor unit 
Indoor unit 
Room A  Room B  Room C  Room D  Room E  Room F 
e.g., charged  
amount (529 oz) 
Refrigerant tubing
Outdoor unit
Very 
small 
room
Indoor unit
Small 
room
Medium 
room
Large room
Mechanical ventilation device – Gas leak detector
0 0 
57 
114 
170 
227 
284 
341 
398 
454 
500 
1000 
1500 
2000 
2500 
3000 
3500 
4000 
400 
200 600 
800 
1000 
1200 
Total amount of refrigerant 
Min.
 indoor v
olume 
Min.
 indoor floor area 
(when the ceiling is 8.8 ft.
 high) 
ft.
3  
ft.
2  
oz 
Range above  
the density limit of  
0.3 oz/ft.
3  
(countermeasures  
needed) 
Range below  
the density limit of  
0.3 oz/ft.
3  
(countermeasures  
not needed) 
SM830157_W-2WAY_ECO-i.indb   3
SM830157_W-2WAY_ECO-i.indb   3
2007/06/08   14:23:11
2007/06/08   14:23:11