IV-4
SM831148
4. Service procedures
(2) LED Indicator Messages on Outdoor Control PCB
Power ON sequence
1. No communication from indoor units in system
2. Communication received from 1 or more indoor units in system
3. Regular communication OK (Capacity and unit quantity match)
If it is not possible to 
advance to 3, repeats 1 
→ 2.
At 3, changes to normal 
control.
P03
Normal operation
Automatic address setting in progress
Automatic address setting alarm (E15)
Automatic address setting alarm (E20)
Automatic address setting alarm (Other than E15 and E20)
EEPROM error (F31)
Blinking alternately
Blinking simultaneously
Blinking simultaneously
Blinking simultaneously
Alarm
LED 1 blinks M times, then LED 2 blinks N times.
The cycle then repeats.
M = 2: P alarm
6: L alarm
N = Alarm No. 
* Refer to 
1. Examples of alarm display
 below.
3: H alarm 4: E alarm 5: F alarm
Alternate blinking during alarms
Insufficient gas indicator
Refrigerant recovery mode
Automatic address setting
Displayed during automatic 
address setting 1 and initial 
communication. After these are 
completed, alarm F31 is displayed.
Pre-trip (P20)
Pre-trip (insufficient gas) 
Pre-trip (other)
(0.25/0.75)
(0.75/0.25)
(0.25/0.75)
(0.75/0.25)
(0.25/0.75)
(0.75/0.25)
ON
:
:
:
LED 1
LED 2
Remarks
OFF
Blinking (0.25/0.75) indicates that the lamp illuminates for 0.25 seconds, and then is OFF for 0.75 seconds. 
Unless otherwise indicated, the blinking is (0.5/0.5).
Note:
This table shows example alarms. Other alarms  
may also be displayed.
P03
P04
P05
P31
H01
E04
F07
L13
( Blinks 2 times )
(
"
 )
(
"
 )
(
"
 )
(Blinks 3 times)
(Blinks 4 times)
(Blinks 5 times)
(Blinks 6 times)
(Blinks 3 times)
(Blinks 4 times)
(Blinks 5 times)
(Blinks 31 times)
(Blinks 1 times)
(Blinks 4 times)
(Blinks 7 times)
(Blinks 13 times)
Alarm / Display
LED 1
Alternately
→ 
→ 
LED 2
(3) Examples of alarm display (other than E15, E16, and E20)