Remote Control Functions
1. Main Operating Functions
2. Automatic Control for Heating and Cooling
Automatic Heating/Cooling Control
(1)  When operation starts, heating or cooling is selected according to the set temperature and the room temperature.
 Room temperature   Set temperature + 2F 
 Cooling
 Set temperature – 2F < Room temperature   Set temperature + 2F 
 Monitoring mode (*1)
 Room temperature < Set temperature – 2F 
 Heating
*1:  If the difference between the room temperature and set temperature is small when operation starts, the cooling 
thermostat remains in standby status (OFF) until the temperature difference increases. When the temperature differ-
ence increases, either cooling operation or heating operation is selected. This standby status is known as “monitoring 
mode.”
(2)  After operation starts in the selected operating mode, the set temperature is automatically shifted by + 4°F (2°C) (cooling 
operation) or – 4°F (2°C) (heating operation).
Example: Temperature set on the remote controller is 68°F (20°C).
Selected operating mode
Shifted set temp.
Remote controller display
1
Cooling
72°F 
(22°C)
68°F 
(20°C)
2
Heating
64°F 
(18°C)
68°F 
(20°C)
(3)  Operating mode changes (heating 
 cooling, cooling 
 heating) which occur during operation as a result of temperature 
changes are handled as shown below.
 Heating 
 cooling: Room temperature 
 Shifted set temperature (set temperature + 4F (2°C)) + 1F (0.5°C)
 Cooling 
 heating: Room temperature 
 Shifted set temperature (set temperature – 4F (2°C)) – 2F (1.0°C)
Example: Temperature set on the remote controller is 68°F (20°C).
Operating mode change
Shifted set temp.
1
Heating 
 Cooling
68 + 4 + 1 = 73°F or higher 
(20 + 2 + 0.5 = 22.5°C or higher) 
(*2)
2
Cooling 
 Heating
68 – 4 – 2 = 62°F or lower
 (20 – 2 – 1.0=17.0°C or lower)
*2:  During heating operation when the body sensor is used, a temperature shift is applied to the intake temperature 
detected by the sensor, in consideration for the difference in temperature at the top and bottom of the room. (Refer 
to the “Room Temperature Control” item.) If this intake shift temperature is 8°F (– 13°C), then the heating 
 cooling 
change occurs when the temperature detected by the body sensor is 80°F (26.5°C) or higher.
(4)  Cooling (heating) operation does not change if the room temperature changes from area C 
 A (or A 
 C) within 10 
minutes after the compressor turns OFF. (Monitoring mode is excepted.)
(5)  When the heating/cooling change 
occurs, the 4-way valve switches 
approximately 30 to 50 seconds 
after the compressor turns ON.
Shifted set temp
Shifted set temp
Selected operating mode
Selected operating mode
Remote controller display
–4 deg
–2 deg
+2 deg
+6 deg
+4 deg
+5 deg
–6 deg
Thermostat
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON OFF
OFF
A
B
C
Heating
Heating
Cooling