Friedrich WY09 Manual Do Utilizador

Página de 44
12
Figure 9
DK (Drain Kit)
In the event that the outdoor temperature drops below 37°F, any water 
chas sis basepan is drained into the sleeve pan on 
that re mains in the 
WE and WY models to prevent freezing.  (NOTE:  In the cooling mode 
of the WS, WE and WY models, condensate over  flow is possible in 
IDK (Interior Drain Kit)
Condensate removal (WS, WE 
and WY models)
If you desire to drain condensate from the basepan during unit opera-
tion, this unit is provided with a drain nipple that can be attached to 
the  basepan.  You  must  provide  a  3/8"  outside  diameter  thin-wall 
plastic or copper tube which will attach to the drain nipple. 
Follow the instructions below:   
STEP 1    Find the drain rubber plug on the rear of the basepan  
and  remove it. (See Figure 10).
STEP 2    Remove the knockout in the lower right side of the rear 
grille. Slide the chassis into the WSD SLEEVE so that the 
drain nipple extends through the knockout.  
STEP 3   Slide the tubing over the drain nipple.
If the chassis must be removed from the sleeve for service, remove 
the clamped drain hose before sliding the chassis out of the sleeve. 
New construction allowing for condensate drain systems built within 
the walls can use the Friedrich Interior Drain Kit (Accessory #IDK).
This kit is designed  for  installation  in  the  bottom  of  the  sleeve 
below the condensate bellows valve (heat/cool models only).   
Reversible Supply 
Grille 45° to 90° 
very humid climates). For these particular instances, an optional 
drain kit (Accessory #DK) is available for water removal.
Return  Air 
Grille
Decorative Front
Screws (4)
Chassis Seal 
Gasket
7
6
5
3
C
6
5
4
3
21
B
A
B
01
A7
0
S

L#E
D
O
M
Moving Object Hazard
     
WARNING
Replace all panels before operating your air  
conditioner. 
Failure to do so can result in severe personal 
injury  or  death  and  damage  to  product  or 
other property. 
Figure 10
Basepan
Drain hose
Drain nipple
Sleeve
Alternate drain kits