Friedrich XQ06M10 Manual Do Utilizador

Página de 47
HEATING ELEMENT (See Figure)
All electric heat models are equipped with  a heating element. 
The EQ08 has a 1.15 KW element. 
The heating element contains a fuse link and a heater limit  
switch. The fuse link is in series with the power supply and 
will    open  and  interrupt  the  power  when  the  temperature 
reaches  199°F  or  a  short  circuit  occurs  in  the  heating 
element.  Once  the  fuse  link  separates,  a  new  fuse  link 
must be installed.  
NOTE:  Always replace with the exact replacement. 
The  heater  element  has  a  high  limit  control.  This  control  
is a bimetal thermostat mounted in the top of the heating  
element. 
Should the fan motor fail or fi lter become clogged, the high  
limit  control  will  open  and  interrupt  power  to  the  heater 
before  reaching an unsafe temperature condition. 
The  control  is  designed  to  open  at  110°F  ±6°F.  Test 
continuity  below 110°F and for open above 110°F. 
TESTING THE HEATING ELEMENT
Testing  of  the  elements  can  be  made  with  an  ohmmeter  
across the terminals after the connecting wires have been  
removed. A cold resistance reading of approximately 10.11 
ohms for the 1.15 KW heater should be registered.  
Figure
Heating Element  
DRAIN PAN VALVE 
During the cooling mode of operation, condensate which  
collects in the drain pan is picked up by the condenser fan  
blade and sprayed onto the condenser coil. This assists 
in cooling the refrigerant plus evaporating the water. 
During the heating mode of operation, it is necessary that 
water be removed to prevent it from freezing during cold 
outside  temperatures.  This  could  cause  the  condenser 
fan blade to freeze in the accumulated water and prevent 
it from turning.  
To provide a means of draining this water, a bellows type 
drain valve is installed over a drain opening in the base 
pan. 
This  valve  is  temperature  sensitive  and  will  open  when 
the  outside  temperature  reaches  40°F.  The  valve  will 
close  gradually  as  the  temperature  rises  above  40°F  to 
fully close at 60°F.  
Figure 26 
Bellows Assembly 
Drain Pan Valve  
COMPONENTS TESTING (Continued)
ELECTRIC SHOCK HAZARD 
WARNING
Disconnect  power  to  the  unit  before 
servicing.  Failure  to  follow  this  warning 
could result in serious injury or death. 
16