Restricted Refrigerant System 
Troubleshooting  a  restricted  refrigerant  system  can  be 
diffi cult. The following procedures are the more common 
problems and solutions to these problems. There are two 
types  of  refrigerant  restrictions:  Partial  restrictions  and 
complete restrictions. 
A  partial  restriction  allows  some  of  the  refrigerant  to 
circulate through the system. 
With  a  complete  restriction  there  is  no  circulation  of 
refrigerant in the system. 
Restricted refrigerant systems display the same symptoms 
as a “low-charge condition.” 
When  the  unit  is  shut  off,  the  gauges  may  equalize  very  
slowly. 
Gauges connected to a completely restricted system will 
run in a deep vacuum. When the unit is shut off, the gauges 
will not equalize at all.
A quick check for either condition begins at the evaporator. 
With a partial restriction, there may be gurgling sounds
at  the  metering  device  entrance  to  the  evaporator.  The 
evaporator in a partial restriction could be partially frosted 
or have an ice ball close to the entrance of the metering 
device. Frost may continue on the suction line back to the 
compressor. 
Often a partial restriction of any type can be found by feel, 
as there is a temperature difference from one side of the 
restriction to the other. 
With a complete restriction, there will be no sound at the 
metering  device  entrance.  An  amperage  check  of  the  
compressor  with  a  partial  restriction  may  show  normal 
current  when  compared  to  the  unit  specifi   cation.  With  a 
complete restriction the current drawn may be considerably 
less than normal, as the compressor is running in a deep 
vacuum (no load.) Much of the area of the condenser will 
be relatively cool since most or all of the liquid refrigerant 
will be stored there. 