Figure 6
Return 
Air Grille
Decorative 
Front
WSC 
Sleeve
AB123456C3
567
MODEL# W
S07A10B
Airflow
Rotate
Discharge 
Grille
1" Diameter Plug
1
1
1
2
2
2
All Friedrich room air conditioners are shipped from the factory with 
a Leakage Current Detection Interrupter (LCDI) equipped power 
cord. The LCDI device meets the UL and NEC requirements for cord 
connected air conditioners effective August 2004.
To test your power supply cord:
1.  Plug power supply cord into a grounded 3 prong outlet.
2. Press RESET (See Figure 7).
3. Press TEST (listen for click; Reset button trips and pops out).
4.   Press and release RESET (listen for click; Reset button 
latches and remains in). The power supply cord is ready for 
operation.
NOTE: LCDI device is not intended to be used as a switch.
Once plugged in the unit will operate normally without the need to 
reset the LCDI device. 
If the device fails to trip when tested or if the power supply cord 
is damaged it must be replaced with a new supply cord from the 
manufacturer. We recommend you contact our Technical Assistance 
Line at (800) 541-6645 ext. 662. To expedite service, please have 
your model and serial number available.
Figure 7
TEST
RESET
WARNING
TEST BEFORE EACH USE
1. PRESS RESET BUTTON
2. PLUG LDCI INTO POWER  
    RECEPTACLE
3. PRESS TEST BUTTON,
    RESET BUTTON SHOULD                  
                 POP UP
4. PRESS TEST BUTTON,  
    FOR USE
DO NOT USE IF ABOVE TEST 
FAILS
WHEN GREEN LIGHT IS ON
IT IS WORKING PROPERLY
RESET
TEST
NOTE: Your LCDI device will resemble one of these illustrations.