EXAMPLE: Airfl ow requirements are calculated as follows: 
(Having a wet coil creates additional resistance to airfl ow. 
This addit ional resistance must be taken into consideration 
to obtain accurate airfl ow information.
 
 
External Static Pressure
External Static Pressure can best be defi ned as the pressure 
difference (drop) between the Positive Pressure (discharge) 
and  the  Negative  Pressure  (intake)  sides  of  the  blower.  
External Static Pressure is developed by the blower as a 
result of resistance to airfl ow (Friction) in the air distribution 
system EXTERNAL to the VERT-I-PAK cabinet.
Resistance applied externally to the VERT-I-PAK (i.e. duct 
work, fi lters, etc.) on either the supply or return side of the 
External Static Pressure is affected by two (2) factors.
1.  Resistance to Airfl ow as already explained.
2.  Blower Speed. Changing to a higher or lower blower 
speed will raise or lower the External Static Pressure  
accordingly.
These affects must be understood and taken into consideration 
when checking External Static Pressure/Airfl ow to insure that 
the system is operating within design conditions.
Operating a system with insuffi cient or excessive airfl ow 
can  cause  a  variety  of  different  operating  problems. 
Among these are reduced capacity, freezing evaporator 
coils, premature compressor and/or heating component 
failures. etc.
System airfl ow should always be verifi ed upon completion 
of a new installation, or before a change-out, compressor 
replacement, or in the case of heat strip failure to insure 
that the failure was not caused by improper airfl ow.
Checking External Static Pressure
The  airflow  through  the  unit  can  be  determined  by 
measuring the external static pressure of the system, and 
consulting the blower performance data for the specifi c 
VERT-I-PAK.
  1.  Set up to measure external static pressure at the 
supply and return air.
  2.  Ensure the coil and fi lter are clean, and that all the 
registers are open.
  3.  Determine  the  external  static  pressure  with  the 
blower operating.
  4.  Refer  to  the  Air  Flow  Data  for  your  VERT-I-PAK 
system to fi nd the actual airfl ow for factory-selected 
fan speeds.
  5.  If the actual airfl ow is either too high or too low, the 
blower speed will need to be changed to appropriate 
setting or the ductwork will need to be reassessed 
and corrections made as required. 
  6.  Select  a  speed,  which  most  closely  provides  the 
required airfl ow for the system.
  7.  Recheck  the  external  static  pressure  with  the 
new  speed.  External  static  pressure  (and  actual 
airfl ow) will have changed to a higher or lower value 
depending upon speed selected. Recheck the actual 
airfl ow  (at  this  "new"  static  pressure)  to  confi rm 
speed selection.
  8.   Repeat  steps  8  and  9  (if  necessary)  until  proper 
airfl ow has been obtained.
system  causes  an  INCREASE  in  External  Static Pres-
sure accompanied by a REDUCTION in airfl ow. 
Determining the Indoor CFM:  Chart A – CFM
Model
VEA12/VHA12
VEA18/VHA18
VEA09/VHA09
ESP (")
.00"
.10"
.20"
.30”
Low
340
300
230
140
High
385
340
280
190
Low
420
350 *
290
250
High
470
420 **
350
300
Low
430
400
340
290
High
480
450
400
330
 
Highlighted values indicate rated performance point.
 
Rated performance for 
VEA12
 
Rated Performance for
**  VHA12
ESP (")
Low
High
.00"
690
740
.10"
610
700
.20"
560
640
.30"
510
580
.40"
450
520
Model
VEA24/VHA24
Highlighted values indicate rated performance point.
15