DRAIN PAN VALVE 
During the cooling mode of operation, condensate which  
collects in the drain pan is picked up by the condenser fan  
blade and sprayed onto the condenser coil. This assists 
in cooling the refrigerant plus evaporating the water. 
During the heating mode of operation, it is necessary that 
water be removed to prevent it from freezing during cold 
outside  temperatures.  This  could  cause  the  condenser 
fan blade to freeze in the accumulated water and prevent 
it from turning.  
To provide a means of draining this water, a bellows type 
drain valve is installed over a drain opening in the base 
pan. 
This valve is temperature sensitive and will open when 
the  outside  temperature  reaches  40°F.  The  valve  will 
close gradually as the temperature rises above 40°F to 
fully close at 60°F.  
TESTING THE HEATING ELEMENTS AND 
LIMIT SWITCHES 
Testing  of  the  heating  elements  can  be  made  with  an 
ohmmeter or continuity tester across the terminals after 
the power wires have been removed. Test the limit switch 
for  continuity  across  its  input  and  output  terminals.Test 
below the limit switch’s reset temperature.
HEATER ELEMENTS AND LIMIT SWITCHES’
SPECIFICATIONS
All  heat  pumps  and  electric  heat  models  are  equipped 
with a heating element and a limit switch (bimetal ther-
mostat). The limit is in series with the element and will 
interrupt the power at a designed temperature.
 
Should the blower motor fail, filter become clogged or air-
flow be restricted etc., the high limit switch will open and 
interrupt the power to the heater before reaching an un-
safe temperature condition.
 
 VPAK 9K, 12K and 18K BTUs Models:
2.5 KW, 230 V, Resistance 18.61 Ohms + - 5%.
Has 1 Limit Switch, Opens at 
120° F, Closes at 90° F,
It has a One Time Open Temp. of
 145° F.
 
3.4 KW, 230 V, Resistance 13.68 Ohms + - 5%.
Has 1 Limit Switch, Opens at 
120° F, Closes at 90° F,
It has a One Time Open Temp. of 
145° F.
 
5 KW, 230 V, Resistance 9.31 Ohms + - 5%.
Has 1 Limit Switch, Opens at
 130° F, Closes at 100° F,
It has a One Time Open Temp. of
 155° F.
 
VPAK 24K BTUs Models:
2.5 KW, 230 V, Resistance 18.61 Ohms + - 5%.
Has 2 Limit Switches, Primary Opens at
 155° F, 
Closes at 
125° F, Secondary’s Open Temp. is 200° F. 
 
3.4 KW, 230 V, Resistance 13.68 Ohms + - 5%.
Has 2 Limit Switches, Primary Opens at
 155° F, 
Closes at 
125° F, Secondary’s Open Temp. is 200° F. 
 
5 KW, 230 V, Resistance 9.31 Ohms + - 5%.
Has 2 Limit Switches, Primary Opens at 
155° F, 
Closes  at 
125° F, Secondary’s Open Temp. is 200° F. 
 
7.5 KW, 230 V (composed of 2, 3.7 KW Elements)
Each Has a Resistance of 
12.41 Ohms + - 5%.
Each Has 2 Limit Switches, Primary Opens at
 165° F, 
Closes at 
135° F With a 1 time Open Temp. of 210° F.
Secondary Limit’s Open Temp. is
 200° F. 
 
10 KW, 230 V (composed of 2, 5 KW Elements)
Each Has a Resistance of
 9.31 Ohms + - 5%.
Each Has 2 Limit Switches, Primary Opens at
 165° F, 
Closes at 
135° F With a 1 time Open Temp. of 210° F.
Secondary Limit’s Open Temp. is
 200° F. 
 
NOTE: Always replace with an exact replacement.
 
 
Bellows Assembly  
Drain Pan Valve  
ComPonEntS tEStIng (Continued)
ELECTRIC SHOCK HAZARD 
WARNING
Disconnect  power  to  the  unit  before 
servicing.  Failure  to  follow  this  warning 
could result in serious injury or death. 