Undercharged Refrigerant Systems 
An undercharged system will result in poor performance 
(low  pressures,  etc.)  in  both  the  heating  and  cooling 
cycle. 
Whenever  you  service  a  unit  with  an  undercharge  of 
refrigerant,  always  suspect  a  leak.  The  leak  must  be 
repaired before charging the unit. 
To  check  for  an  undercharged  system,  turn  the  unit  on, 
allow  the  compressor  to  run  long  enough  to  establish 
working pressures in the system (15 to 20 minutes). 
During the cooling cycle you can listen carefully at the exit 
of the metering device into the evaporator; an intermittent  
hissing  and  gurgling  sound  indicates  a  low  refrigerant 
charge. Intermittent frosting and thawing of the evaporator 
is  another  indication  of  a  low  charge,  however,  frosting 
and  thawing  can  also  be  caused  by  insufficient  air  over 
the evaporator. 
Checks for an undercharged system can be made at 
the compressor. If the compressor seems quieter than 
normal, it is an indication of a low refrigerant charge.  
overcharged Refrigerant Systems
A  check  of  the  amperage  drawn  by  the  compressor 
motor  should  show  a    lower  reading.  (Check  the  Unit 
Specification.)    After  the  unit  has  run  10  to  15  minutes, 
check the gauge pressures. Gauges connected to system 
with  an  undercharge  will    have  low  head  pressures  and 
substantially low suction  pressures.  
of  the  evaporator  will  not  be  encountered  because  the 
refrigerant  will  boil  later  if  at  all.  Gauges  connected  to 
system will usually have higher head pressure (depending 
upon amount of over charge). Suction pressure should be 
slightly higher. 
Compressor  amps  will  be  near  normal  or  higher. 
Noncondensables  can  also  cause  these  symptoms.  To 
confirm, remove some of the charge, if conditions improve, 
system may be overcharged. If conditions don’t improve, 
Noncondensables are indicated. 
Whenever  an  overcharged  system  is  indicated,  always 
make  sure  that  the  problem  is  not  caused  by  air  flow 
problems. Improper air flow over the evaporator coil may 
indicate some of the same symptoms as an over charged 
system. 
An overcharge can cause the compressor to fail, since it  
would be “slugged” with liquid refrigerant. 
The charge for any system is critical. When the compressor 
is noisy, suspect an overcharge, when you are sure that 
the air quantity over the evaporator coil is correct. Icing   
ELECTRIC SHOCK HAZARD 
WARNING
Turn  off  electric  power  before  service  or 
installation.
Extreme  care  must  be  used,  if  it  becomes 
necessary  to  work  on  equipment  with  power 
applied.
Failure to do so could result in serious injury or 
death.
Sealed Refrigeration System contains refrigerant 
and oil under high pressure.
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with refrigerants.
Failure to follow these procedures could 
result in serious injury or death. 
WARNING
HIGH PRESSURE HAZARD 
28