Installation of the system must be done in accordance with all state and local 
building codes.  
The condensing unit and unit cooler are connected by a liquid line and an 
insulated suction line that are supplied by the installer. These lines must be 
properly sized for the distance between the two units. After the units and the lines 
are installed, the system must be pressure tested. If no leaks are found, 
evacuate and charge system with R134A. Refrigerant amount will vary 
depending on the length of line set. 
 
3. Air Sensor 
 
The air sensor is recommended to place in the wine room. If it is in a return duct, 
the temperature differential may lead to erroneous readings. 
 
4. Electrical Wiring 
 
•  We strongly recommend against the use of an extension cord. However, if 
you still select to use an extension cord, it is absolutely necessary that it is 
a UL LISTED 3-wire grounding type appliance extension cord. The 
marked rating of the extension cord should be 115 V, 20 A. or equivalent 
and not greater than 15ft in length. 
 
1) Customer Wiring