Toshiba RAV-SM801AT-E Manual Do Utilizador

Página de 139
– 8 –
RAV-SM561AT-E,  RAV-SM801AT-E
1000 
or more
300 
or more
1500
 or more
2000 
or more
200 
or more
300 
or more
300 
or more
1000 
or more
200 
or more
1000 
or more
1000  or more
1000  or more
150 
or more
<Obstacle also at the upper side>
Obstacles at both front and rear sides
Open the upper side and both right and left sides.
The height of obstacle at both front and rear side,
should be lower than the height of the outdoor unit.
<Standard installation>
1. Single unit installation
2. Serial installation of two or more units
Serial installation at front and rear sides
Open the upper side and both right and left sides.
The height of obstacle at both front and rear sides
should be lower than the height of the outdoor unit.
<Standard installation>
Drain nipple
Waterproof rubber cap
Installation of Outdoor Unit
• Before installation, check strength and horizontality
of the base so that abnormal sound does not
generate.
• According to the following base diagram, fix the
base firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
15 or less
• In case of draining through the drain hose, attach
the following drain nipple and the waterproof rubber
cap, and use the drain hose (Inner diam.: 16 mm)
sold on the market. And also seal the screws
securely with silicone material, etc. so that water
does not drop down. Some conditions may cause
dewing or dripping of water.
3
SELECTION OF INSTALLATION
Waterproof 
rubber cap
Base plate
Drain nipple
For Reference
If a heating operation would be continuously per-
formed for a long time under the condition that the
outdoor temperature is 0°C or lower, draining of
defrosted water may be difficult due to freezing of the
bottom plate, resulting in a trouble of the cabinet or
fan.
It is recommended to procure an anti-freeze heater
locally for a safety installation of the air conditioner.
For details, contact the dealer.
600
108
90
90
306
60
330
Ø28 Drain hole
Set the out margin of the
anchor bolt to 15 mm or less.