Toshiba RAV-SM2804AT7ZG Manual Do Utilizador

Página de 133
 109 
EN
25
Digital Inverter
H
A
Nitrogen gas pressure 0.5 MPa
Existing pipes: Cannot be used. 
• Use new pipes.
Connect the indoor/outdoor units to the existing pipe. 
• Use a flare nut attached to the main unit for the 
indoor/outdoor units. (Do not use the flare nut of the 
existing pipe.)
• Re-machine the flare machining size to size for R410A.
When using a Ø19.1 mm pipe for the gas pipe of the first 
branching pipe
•  After the existing air conditioner is operated in cooling 
mode for approx. 30 minutes or longer,* recover the 
refrigerant.
•  For cleaning the pipes and recovering oil
•  Refrigerant recovery: Refrigerant recovery equipment
•  (Airtight test), Vacuum dry, Refrigerant charge, Gas leak 
check
• Remove the existing air conditioner from the piping and 
carry out flushing (nitrogen pressure 0.5 MPa) to remove 
any remains inside of the pipe.
Was largely discolored oil or a large quantity 
of remains discharged? (When the oil 
deteriorates, the color of the oil changes to a 
muddy or black color.)
(If there is discharge of remains, it is judged that a 
large quantity of remains are present.)
Piping necessary to change the flare nut/
machining size due to pipe compression
Clean the pipes or use new pipes.
In case of twin pipes, also be sure to flush the 
branching pipe.
Note]
Turn the existing pipe switch on the cycle control P.C. 
board of the outdoor unit to ON side. At shipment from 
factory OFF 
 ON for existing pipe (Refer to the table 
below.) (Be sure to set the contents in the table below 
in order to restrict the refrigerating cycle pressure of 
the equipment in the pipe standard.)
Existing pipe SW
Trial run
1) Flare nut width: H
2) Flare machining size: A
(mm)
(mm)
Becomes a little larger for R410A
For R410A
For R22
Copper pipe 
outer 
diameter
For R410A
For R22
Same as above
Same as 
above
Do not apply refrigerator oil to the flare surface.
Bit 3 of SW802 
ON 
 
 
Switch
Ø6.4
Ø9.5
Ø12.7
Ø15.9
Ø19.1
17
22
26
29
36
24
27
Ø6.4
Ø9.5
Ø12.7
Ø15.9
Ø19.1
9.1
13.2
16.6
19.7
24.0
9.0
13.0
16.2
19.4
23.3
 
Copper pipe 
outer 
diameter
 
NO
YES
YES
YES
NO
NO
Are there scratches or dents on the existing pipes?
Is it possible to operate the existing air conditioner?