5.  Refrigerant piping design
1.  Warnings on refrigerant leakage
Check of concentration limit
The room in which the air conditioner is to be installed requires a design that ensures that the concentration of 
refrigerant gas will not exceed a set limit if there is a leak.
Refrigerant R-410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, 
and is not restricted by laws that protect the ozone layer. However, since it contains more than air, it poses the 
risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R-410A is almost non-
existent. With the recent increase in the number of high concentration buildings, however, the installation of multi 
air conditioner systems is on the increase because of the need for effective use of floor space, individual control, 
energy conservation by curtailing heat and carrying power, etc.
 
Most importantly, the multi air conditioner system is able to contain a large amount of refrigerant compared with 
conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, 
select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration 
does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).
 
In a room where the concentration may exceed the limit, create an opening to adjacent rooms, or install mechanical 
ventilation combined with a gas leak detection device. The concentration is as given below. 
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
≤ Concentration limit (kg/m³) 
The concentration limit of R-410A which is used in multi air conditioners is 0.3 kg/m³.
Note 2: The standards for minimum room volume are as 
follows:
(1)  No partition (shaded portion)
(2)  When there is an effective opening with the adjacent 
room for ventilation of leaking refrigerant gas (opening 
without a door, or an opening 0.15% or larger than the 
respective floor spaces at the top or bottom of the door).
(3)  If an indoor unit is installed in each partitioned room and 
the refrigerant piping is interconnected, the smallest 
room is the critical room. But when a mechanical 
ventilation device is installed in combination with a gas 
leak detector in the smallest room where the density 
limit is exceeded, the volume of the next smallest 
room is used.
Note 1: If there are 2 or more refrigeration systems in 
a single refrigeration device, the amounts of refrigerant 
should be as charged in each independent device.
For the amount of charge in this example: 
• 
The possible amount of leaked refrigerant gas in 
rooms A, B and C is 10 kg.
• 
The possible amount of leaked refrigerant gas in 
rooms D, E and F is 15 kg.
Mechanical ventilation device - gas leak detector
Outdoor unit
e.g. charged amount (15 kg)
e.g. charged 
amount (10 kg)
Room A
Room B
Room C
Room D
Room E
Room F
Indoor unit
Outdoor unit
Indoor unit
Refrigerant piping
Refrigerant piping
Outdoor unit
Indoor unit
Large room
Medium room
Small 
room
Very 
small 
room