Trane XR15 Manual Do Utilizador

Página de 16
Trane
www.trane.com
 
 
 
10/10
Trane has a policy of continuous product and product data improvement and it reserves the right to change 
design and specifications without notice.
Mechanical 
 Specification Options
General
The 4TTR5 is fully charged from the
factory for up to 15 feet of piping. This
unit is designed to operate at outdoor
ambient temperatures as high as 115°F.
Cooling capacities are matched with
a wide selection of air handlers and
furnace coils that are AHRI certified. The
unit is certified to UL 1995. Exterior is
designed for outdoor application.
Casing
Unit casing is constructed of heavy
gauge, G90 galvanized steel and
painted with a weather-resistant powder
paint  
on all louvers, panels, prepaint on all
other panels. Corrosion and weather-
proof CMBP-G30 DuraTuff™ base.
Refrigerant Controls
Refrigeration system controls include
condenser fan and compressor contac-
tor. High and low pressure controls are
inherent to the compressor. A factory
installed liquid line drier is standard.
Compressor
The Climatuff
®
compressor features
internal over temperature and pressure
protection and total dipped hermetic
motor. Other features include: roto lock
suction and discharge refrigerant con-
nections, centrifugal oil pump and low
vibration and noise.
Condenser Coil
The outdoor coil provides low airflow
resistance and efficient heat transfer.  
The coil is protected on all four sides by
louvered panels.
Low Ambient Cooling
As manufactured, this unit has a cool-
ing capability to 55°F. The addition of
an evaporator defrost control with TXV
permits low ambient cooling to 30° F.
accessories
Thermostats — Cooling only and heat/
cooling (manual and automatic change-
over). Sub-base to match thermostat
and locking thermostat cover.