York DY 060 Manual Do Utilizador

Página de 36
343615-YTG-B-0308
30
Johnson Controls Unitary Products
FIGURE 10 -FOUR AND SIX POINT LOADING
44
7
/
8
82
1
/
4
Y
X
A
B
C
D
CONDENSER COIL
END OF UNIT
FRONT OF UNIT
APPROXIMATE
CENTER OF GRAVITY
BACK OF UNIT
44
7
/
8
82
1
/
4
Y
X
A
B
C
D
E
F
CONDENSER COIL
END OF UNIT
FRONT OF UNIT
APPROXIMATE
CENTER OF GRAVITY
BACK OF UNIT
TABLE 30: DY 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT
TOTAL
4-Point Loading (lb)
6-Point Loading (lb)
A
B
C
D
A
B
C
D
E
F
DY036 Cooling/ Electric
575
132
125
155
164
89
85
82
102
106
110
DY036N04
615
141
133
166
175
95
91
88
110
114
118
DY036D06
625
143
135
168
178
96
93
89
111
115
120
DY036N08
635
145
138
171
181
98
94
91
113
117
122
DY036D10
645
148
140
174
184
99
96
92
115
119
124
DY048 Cooling/ Electric
585
134
127
158
167
90
87
84
104
108
112
DY048(D,N)06
635
145
138
171
181
98
94
91
113
117
122
DY048(D,N)10
655
150
142
177
187
101
97
94
117
121
125
DY060 Cooling/ Electric
590
135
128
159
168
91
88
84
105
109
113
DY060D06
640
147
139
173
182
99
95
92
114
118
123
DY060N08
650
149
141
175
185
100
97
93
116
120
125
DY060(D,N)10
660
151
143
178
188
102
98
95
118
122
126
TABLE 31: CENTER OF GRAVITY
DIMENSION
3 - 5 TON
X
40”
Y
20”