York DM150 Manual Do Utilizador
036-21044-003-A-0304
Unitary Products
15
TABLE 5: COOLING CAPACITY 26.4 KW UNIT - METRIC
Air On
Evap. Coil
Temperature of Air on Condenser Coil 29°C
Temperature of Air on Condenser Coil 35°C
m
3
/s
WB
(°C)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°F)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°C)
30
28
27
25
23
22
20
30
28
27
25
23
22
20
1.06
22
31
8.6
18
16
14
12
10
-
-
29
9.2
17
15
13
11
9
-
-
19
28
8.4
22
20
18
16
14
12
10
26
9.0
21
19
17
15
13
11
9
17
26
8.2
26
24
22
20
18
16
14
24
8.6
24
22
20
18
16
15
13
14
25
8.2
25
24
23
21
19
17
15
23
8.6
23
23
21
19
17
15
13
1.24
22
31
8.7
19
17
15
13
10
-
-
30
9.3
18
16
14
12
9
-
-
19
29
8.5
24
22
19
17
15
13
10
27
9.1
23
21
18
16
14
12
10
17
27
8.3
26
26
24
21
19
17
15
24
8.7
24
24
22
20
18
15
13
14
25
8.2
25
25
24
22
20
18
15
24
8.7
24
23
23
20
18
16
14
1.42
22
32
8.8
21
19
16
13
11
-
-
31
9.4
20
18
15
13
10
-
-
19
30
8.6
26
23
21
18
16
13
10
28
9.2
25
23
20
17
15
12
10
17
27
8.3
27
27
25
23
20
18
15
25
8.8
25
25
24
21
19
16
14
14
26
8.3
26
26
26
24
21
18
16
24
8.8
24
24
24
22
19
17
14
1.59
22
33
8.8
23
20
17
14
11
-
-
31
9.4
22
19
16
13
10
-
-
19
30
8.6
28
25
22
19
16
13
10
28
9.2
27
24
21
18
15
12
9
17
28
8.4
28
28
27
24
21
18
15
25
8.9
25
25
25
22
19
16
13
14
27
8.3
27
27
27
24
21
18
15
25
8.9
25
25
25
22
19
16
13
1.77
22
34
8.9
24
21
18
14
11
-
-
32
9.5
23
20
17
13
10
-
-
19
31
8.7
29
26
23
20
16
13
10
29
9.3
29
25
22
19
15
12
9
17
28
8.4
28
28
28
25
21
18
15
26
8.9
26
26
26
23
19
16
13
14
27
8.4
27
27
27
24
21
17
14
25
8.9
25
25
25
22
19
15
12
Temperature of Air on Condenser Coil 41°C
Temperature of Air on Condenser Coil 46°C
1.06
22
27
9.8
16
14
12
10
8
-
-
25
10.4
15
13
11
9
8
-
-
19
24
9.5
20
18
16
14
12
10
8
21
10.0
19
17
15
13
11
9
7
17
21
9.1
21
21
19
17
15
13
11
19
9.7
19
19
17
15
14
12
10
14
21
9.1
21
21
19
17
15
13
11
19
9.7
19
19
17
15
13
11
10
1.24
22
28
9.9
18
15
13
11
9
-
-
25
10.5
17
15
12
10
8
-
-
19
25
9.6
22
20
17
15
13
11
8
22
10.1
21
19
16
14
12
10
7
17
22
9.3
22
22
20
18
16
14
12
20
9.8
20
20
19
17
14
12
10
14
22
9.3
22
22
21
18
16
14
12
20
9.8
20
20
19
16
14
12
10
1.42
22
28
10.0
19
17
14
12
9
-
-
26
10.6
19
16
13
11
8
-
-
19
25
9.7
24
21
19
16
14
11
9
23
10.2
23
20
18
15
13
10
7
17
23
9.4
23
23
22
20
17
14
12
21
9.9
21
21
21
18
15
13
10
14
22
9.4
22
22
22
20
17
15
12
20
9.9
20
20
20
18
15
12
10
1.59
22
29
10.1
21
18
15
12
9
-
-
27
10.7
20
17
14
11
8
-
-
19
26
9.8
25
23
20
17
14
11
8
23
10.3
23
22
19
16
13
10
7
17
23
9.4
23
23
23
20
17
14
11
21
10.0
21
21
21
18
15
12
9
14
23
9.4
23
23
23
20
17
14
11
21
10.0
21
21
21
18
15
12
9
1.77
22
29
10.1
22
19
16
13
9
-
-
27
10.8
21
18
15
12
8
-
-
19
26
9.8
26
24
21
18
14
11
8
24
10.4
24
23
20
16
13
10
7
17
24
9.5
24
24
24
20
17
14
11
21
10.1
21
21
21
18
15
12
8
14
23
9.5
23
23
23
20
17
13
10
21
10.1
21
21
21
18
14
11
8
Temperature of Air on Condenser Coil 52°C
1.06
22
23
11.0
14
12
11
9
7
-
-
19
19
10.5
18
16
14
12
10
8
6
17
17
10.2
17
17
16
14
12
10
8
14
17
10.2
17
17
15
13
12
10
8
1.24
22
23
11.1
16
14
12
9
7
-
-
19
20
10.6
20
17
15
13
11
9
6
17
18
10.3
18
18
17
15
13
11
9
14
18
10.3
18
18
17
14
12
10
8
1.42
22
24
11.2
18
15
13
10
7
-
-
19
20
10.8
20
19
17
14
11
9
6
17
18
10.4
18
18
18
16
14
11
9
14
18
10.5
18
18
18
16
13
10
8
1.59
22
25
11.4
19
16
13
10
7
-
-
19
21
10.9
21
20
18
15
12
9
6
17
19
10.5
19
19
19
16
13
10
7
14
19
10.6
19
19
19
16
13
10
7
1.77
22
25
11.5
21
17
14
11
8
-
-
19
21
11.0
21
21
19
15
12
9
5
17
19
10.6
19
19
19
16
12
9
6
14
19
10.7
19
19
19
16
12
9
6
1 These capacities are gross ratings. For net
capacity, deduct air blower motor. Refer to the
appropriate Blower Performance Table for the
kW of the supply air blower motor.
appropriate Blower Performance Table for the
kW of the supply air blower motor.
2 These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
air blower motor.