York DJ 300 Manual Do Utilizador
261660-YTG-D-0708
12
Johnson Controls Unitary Products
TABLE 6: COOLING CAPACITIES FOR DJ240
Air on Evaporator Coil
Temperature of Air on Condenser Coil
85°F
95°F
CFM
WB
(°F)
(°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
6000
72
273.1 16.90 149.8 132.7 115.6 98.5 81.4
-
-
257.3 18.45 150.2 133.1 116.0 98.9 81.8
-
-
67
248.6 16.43 197.6 180.5 163.4 146.3 129.1 112.0 94.9 237.3 17.83 192.3 175.1 158.0 140.9 123.8 106.7 89.6
62
231.2 16.44 227.9 210.8 193.7 176.6 159.5 142.4 125.3 215.2 17.64 215.2 200.8 183.7 166.6 149.5 132.4 115.3
57
216.6 15.98 216.6 210.2 193.1 176.0 158.9 141.8 124.7 221.2 17.98 221.2 213.2 196.1 179.0 161.8 144.7 127.6
7000
72
278.7 16.96 165.8 145.6 125.4 105.1 84.9
-
-
264.7 18.51 167.2 146.9 126.7 106.5 86.3
-
-
67
253.8 16.49 217.5 197.3 177.1 156.9 136.7 116.5 96.2 244.2 17.89 213.1 192.9 172.7 152.4 132.2 112.0 91.8
62
236.0 16.50 234.4 225.8 210.0 189.8 169.6 149.4 129.2 221.5 17.70 221.5 214.3 200.7 180.5 160.3 140.0 119.8
57
221.1 16.04 221.1 217.9 209.3 189.1 168.9 148.7 128.5 227.6 18.04 227.6 223.6 214.2 194.0 173.8 153.5 133.3
8000
72
284.4 17.02 181.8 158.4 135.1 111.8 88.4
-
-
272.2 18.58 184.1 160.8 137.4 114.1 90.8
-
-
67
259.0 16.55 237.5 214.2 190.9 167.5 144.2 120.9 97.6 251.0 17.95 233.9 210.6 187.3 164.0 140.6 117.3 94.0
62
240.8 16.56 240.8 240.8 226.3 203.0 179.7 156.4 133.0 227.7 17.76 227.7 227.7 217.7 194.4 171.0 147.7 124.4
57
225.6 16.10 225.6 225.6 225.6 202.3 178.9 155.6 132.3 234.0 18.10 234.0 234.0 232.3 209.0 185.7 162.4 139.0
8700
72
291.0 17.43 193.1 167.5 141.8 116.1 90.4
-
-
277.5 18.98 195.6 169.9 144.2 118.5 92.9
-
-
67
265.0 16.95 251.7 226.0 200.3 174.7 149.0 123.3 97.6 256.0 18.33 247.4 222.2 196.5 170.8 145.2 119.5 93.8
62
246.4 16.96 246.4 246.4 237.6 211.9 186.2 160.5 134.9 232.2 18.14 232.2 232.2 227.2 201.5 175.8 150.1 124.5
57
230.8 16.49 230.8 230.8 230.8 205.2 179.5 153.8 128.1 238.6 18.50 238.6 238.6 237.7 212.1 186.4 160.7 135.0
9400
72
297.7 17.84 204.5 176.5 148.5 120.5 92.4
-
-
282.9 19.38 207.0 179.0 151.0 123.0 94.9
-
-
67
271.0 17.35 265.8 237.8 209.8 181.8 153.7 125.7 97.7 260.9 18.72 260.9 233.7 205.7 177.7 149.7 121.7 93.6
62
252.0 17.36 252.0 252.0 248.8 220.7 192.7 164.7 136.7 236.6 18.53 236.6 236.6 236.6 208.6 180.6 152.6 124.6
57
236.1 16.88 236.1 236.1 236.1 208.1 180.1 152.0 124.0 243.2 18.89 243.2 243.2 243.2 215.1 187.1 159.1 131.1
105°F
115°F
6000
72
244.1 20.09 146.5 129.4 112.3 95.2 78.1
-
-
230.8 21.72 142.8 125.7 108.6 91.5 74.4
-
-
67
225.3 19.63 186.7 169.6 152.5 135.4 118.3 101.2 84.1 213.4 21.43 181.2 164.1 147.0 129.9 112.8 95.7 78.6
62
202.7 19.37 202.7 194.9 177.7 160.6 143.5 126.4 109.3 190.2 21.09 190.2 188.9 171.8 154.7 137.6 120.5 103.4
57
211.7 19.63 211.7 205.7 188.6 171.5 154.4 137.3 120.2 202.2 21.28 202.2 198.2 181.1 164.0 146.9 129.8 112.7
7000
72
250.6 20.15 162.5 142.2 122.0 101.8 81.6
-
-
236.4 21.79 157.8 137.5 117.3 97.1 76.9
-
-
67
231.3 19.69 206.2 185.9 165.7 145.5 125.3 105.1 84.9 218.5 21.50 199.2 179.0 158.8 138.6 118.4 98.1 77.9
62
208.1 19.43 208.1 204.2 193.1 172.9 152.7 132.5 112.3 194.8 21.16 194.8 194.1 185.6 165.4 145.1 124.9 104.7
57
217.3 19.70 217.3 214.3 204.9 184.7 164.5 144.3 124.1 207.0 21.35 207.0 205.1 195.7 175.4 155.2 135.0 114.8
8000
72
257.0 20.22 178.4 155.1 131.7 108.4 85.1
-
-
241.9 21.87 172.7 149.4 126.0 102.7 79.4
-
-
67
237.3 19.76 225.6 202.3 178.9 155.6 132.3 109.0 85.6 223.6 21.58 217.3 193.9 170.6 147.3 123.9 100.6 77.3
62
213.5 19.50 213.5 213.5 208.5 185.2 161.9 138.5 115.2 199.4 21.24 199.4 199.4 199.4 176.0 152.7 129.4 106.1
57
222.9 19.77 222.9 222.9 221.3 197.9 174.6 151.3 128.0 211.9 21.43 211.9 211.9 210.2 186.9 163.5 140.2 116.9
8700
72
264.1 20.56 191.3 165.6 139.9 114.3 88.6
-
-
250.6 22.15 187.0 161.3 135.6 110.0 84.3
-
-
67
243.8 20.09 238.0 215.7 190.0 164.4 138.7 113.0 87.3 231.7 21.85 228.5 209.3 183.6 157.9 132.2 106.6 80.9
62
219.4 19.83 219.4 219.4 216.9 191.2 165.5 139.8 114.2 206.6 21.51 206.6 206.6 206.6 180.9 155.2 129.5 103.9
57
229.0 20.10 229.0 229.0 228.2 202.5 176.9 151.2 125.5 219.5 21.70 219.5 219.5 218.7 193.0 167.3 141.7 116.0
9400
72
271.1 20.91 204.1 176.1 148.1 120.1 92.1
-
-
259.4 22.43 201.3 173.3 145.2 117.2 89.2
-
-
67
250.3 20.43 250.3 229.2 201.1 173.1 145.1 117.1 89.1 239.7 22.13 239.7 224.6 196.6 168.6 140.5 112.5 84.5
62
225.2 20.16 225.2 225.2 225.2 197.2 169.2 141.1 113.1 213.8 21.78 213.8 213.8 213.8 185.7 157.7 129.7 101.7
57
235.2 20.43 235.2 235.2 235.2 207.1 179.1 151.1 123.1 227.2 21.98 227.2 227.2 227.2 199.2 171.1 143.1 115.1
125°F
6000
72
217.6 23.35 139.1 122.0 104.9 87.8 70.7
-
-
67
201.4 23.23 175.7 158.6 141.5 124.4 107.3 90.2 73.1
62
177.7 22.82 177.7 177.7 165.8 148.7 131.6 114.5 97.4
57
192.7 22.93 192.7 190.8 173.7 156.5 139.4 122.3 105.2
7000
72
222.2 23.43 153.1 132.8 112.6 92.4 72.2
-
-
67
205.6 23.31 192.3 172.1 151.9 131.7 111.4 91.2 71.0
62
181.5 22.90 181.5 181.5 178.0 157.8 137.6 117.4 97.1
57
196.8 23.01 196.8 195.8 186.4 166.2 146.0 125.7 105.5
8000
72
226.8 23.51 167.0 143.7 120.3 97.0 73.7
-
-
67
209.9 23.39 208.9 185.6 162.3 138.9 115.6 92.3 68.9
62
185.2 22.98 185.2 185.2 185.2 166.9 143.5 120.2 96.9
57
200.8 23.09 200.8 200.8 199.1 175.8 152.5 129.1 105.8
8700
72
237.2 23.74 182.7 157.0 131.3 105.7 80.0
-
-
67
219.5 23.61 219.0 202.8 177.1 151.5 125.8 100.1 74.4
62
193.7 23.19 193.7 193.7 193.7 170.6 144.9 119.2 93.6
57
210.0 23.30 210.0 210.0 209.2 183.5 157.8 132.1 106.5
9400
72
247.6 23.96 198.4 170.4 142.4 114.3 86.3
-
-
67
229.1 23.84 229.1 220.0 192.0 164.0 136.0 107.9 79.9
62
202.3 23.41 202.3 202.3 202.3 174.3 146.3 118.2 90.2
57
219.2 23.52 219.2 219.2 219.2 191.2 163.2 135.1 107.1
1.
The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
Performance table for the kW of the supply air blower motor.
2.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.