York AHE18 THRU 60' Manual Do Utilizador

Página de 14
Johnson Controls Unitary Products
5
680210-YTG-B-0311
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow (CFM)
80%
90%
100%
110%
120%
Capacity Factor
0.96
0.98
1.00
1.02
1.03
PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models
AHE18B
AHE24B
AHE30B
AHE36C
AHE42D
AHE48D
AHE60D
Blower - Diameter x Width
10 x 8
10 x 8
10 x 8
11 x 10
11 x 10
11 x 10
11 x 10
Motor
HP
1/3 HP
1/3 HP
 1/3 HP
1/2 HP
1/2 HP
3/4 HP
3/4 HP
Nominal RPM
1050
1050
1050
1050
1050
1050
1050
Voltage
208/230
208/230
208/230
208/230
208/230
208/230
208/230
Amps
Full Load (230)
2.8
2.8
2.8
4.1
4.1
6.0
6.0
Filter
1
Type
DISPOSABLE OR PERMANENT
Size
16 x 20 x 1
16 x 20 x 1
16 x 20 x 1
20 x 20 x 1
22 x 20 x 1
22 x 20 x 1
22 x 20 x 1
Permanent Type Kit
1PF0601BK
1PF0601BK
1PF0601BK
1PF0602BK
1PF0603BK
1PF0603BK
1PF0603BK
Shipping / Operating Weight (lbs.)
115/103
120/105
120/105
152/137
168/150
171/153
174/156
1.  Field Supplied.
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
FOR
208V
OPERATION MULTIPLY
240V
TABULATED KW & MBH BY
.751
230V
240V
.918
220V
240V
.840
ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models
Total Motor Amps
Minimum Circuit Ampacity
Max. O.C.P.
1
Amps/Type
Minimum Wire 
Size A.W.G.
60 Hertz
60 Hertz
208V
230V
208V
230V
AHE MODELS
AHE18B3XH21
2.8
2.8
3.5
3.5
15
14
AHE24B3XH21
2.8
2.8
3.5
3.5
15
14
AHE30B3XH21
2.8
2.8
3.5
3.5
15
14
AHE36C3XH21
4.1
4.1
5.1
5.1
15
14
AHE42D3XH21
4.1
4.1
5.1
5.1
15
14
AHE48D3XH21
6.0
6.0
7.5
7.5
15
14
AHE60D3XH21
6.0
6.0
7.5
7.5
15
14
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
*
May be 0 (no Circuit Breaker) or 1 (with Circuit Breaker).