Aluminum Finned Copper Coils:
Grooved tubing and enhanced louvered
fin for maximum heat transfer and
energy efficiency.
Twin Blowers:
Move air quietly.  Most models feature
multispeed blower motors providing
airflow adjustment for high and low
static operation.  Motor overload
protection is standard on all models.
Air Conditioner Compressor:
Scroll Compressors eliminate need for
crankcase heater.  Standard on all
models.
R-410A Refrigerant:
Designed with R-410A (HFC) non-
ozone depleting refrigerant in
compliance with the Montreal protocol
and 2010 EPA requirements.
Phase Rotation Monitor:
Standard on all 3 phase scroll
compressors.  Protects against reverse
rotation if power supply is not properly
connected.
Galvanized 20 Gauge Zinc Coated
Steel Cabinet:
Cleaned, rinsed, sealed and dried
before the polyurethane primer is
applied.  The cabinet is handsomely
finished with a baked on textured
enamel, which allows it to withstand
1000 hours of salt spray tests per
ASTM B117-03.
Foil Faced Insulation:
Standard on all units.
Full Length Mounting Brackets:
Built into cabinet for improved
appearance and easy installation.
NOTE: Bottom mounting bracket
included to assist in installation.
Electrical Components:
Are easily accessible for routine
inspection and maintenance through a
right side, service panel opening.
Features a lockable, hinged access
cover to the circuit breaker or toggle
disconnect switch.
Electric Heat Strips:
Features an automatic limit and thermal
cut-off safety control.  Heater packages
can be factory or field installed for all 1
½
through 6 ton models.
Filter Service Door:
Separate service door provides easy
access for filter change.
One Inch, Disposable Air Filters:
Are standard equipment.  Optional one
inch washable filters available and filter
racks permit the addition of 2" pleated
filter.  Factory or field installed.
Condenser Fan and Motor
Shroud Assembly:
Slides out for easy access.
Barometric Fresh Air Damper:
Standard on all units.  Allows up to 25%
outside fresh air.  Optional ventilation
packages available.
Built-in Circuit Breakers:
Standard on all electric heat versions of
single (230/208 volt) and three phase
(230/208 volt) equipment.  Toggle
disconnects are standard on all electric
heat versions of three phase (460 volt)
equipment.
Slope Top:
Standard feature for water run-off.
Top Rain Flashing:
Standard feature on all models.
The Bard Wall-Mount Air Conditioner is a self contained energy efficient
system, which is designed to offer maximum indoor comfort at a minimal
cost without using valuable indoor floor space or outside ground space.
This unit is the ideal product for versatile applications such as:  new
construction, modular offices, school modernization, telecommunication
structures, portable structures or correctional facilities.  Factory or field
installed accessories are available to meet specific job requirements.
Liquid Line Filter Drier:
Standard on all units.  Protects system
against moisture.
Compressor Control Module:
Standard on all units.  Built-in off-delay
timer adjustable from 30 seconds to 5
minutes.  2-minute on-delay if power
interrupt.  120-second bypass for low
pressure control, and both soft and
manual lockouts for high and low
pressure controls.  Alarm output for
alarm relay.
High & Low Pressure Switches are
Auto-Reset:
Standard on all units.  Built-in lockout
circuit resets from the room thermostat.
Provides commercial quality protection to
the compressor.
G
REEN
 R
EFRIGERANT
R-410A
 Engineered Features
 Models  W24A to W70A and W24L to W70L
 21,200 Btuh (6.21 KW) – 59,000 Btuh (17.28 KW)
 Right Side Control Panel
50Hz
THE WALL-MOUNT™ AIR CONDITIONERS (50HZ)