S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
36
Lead Lag Slave Configuration 
Parameters (Hydronic Control Only)
Table 34 displays Lead Lag Slave Configuration parameters.
Fig. 68. Lead Lag slave configuration.
Lead Lag Master Configuration 
Parameters (Hydronic Control Only)
Table 35 displays Lead Lag Master Configuration parameters.
Click the Advanced Settings button to see available advanced 
parameters as shown in Table 36–44.
Use the left and right arrows to switch between Modulation, 
CH, DHW, Frost Protection, Warm Weather Shutdown, 
Algorithms, Rate Allocation, Add stage and Drop stage 
parameters.
Fig. 69. Lead Lag master configuration and Advanced 
Settings button.
Table 34. Lead Lag Slave 
Configuration Parameters.
Parameter
Comment
Slave enable
Slave
ModBUS slave
Disabled
Slave mode
Use first
Use last
Equalize run time
Base load rate
0–6000 rpm
Slave sequence 
order
0–8
Demand to firing 
delay
___hour ___min ___sec
Fan rate during off 
cycle
0–12000 rpm
ModBus port
MB1
MB2
No port
ModBus address
0–250
Table 35. Lead Lag Master Configuration Parameters.
Parameter
Comment
Master enable
Enabled
Disabled
CH setpoint
-40 °F to 266 °F (-40 °C to 130 °C)
CH time of day 
setpoint
-40 °F to 266 °F (-40 °C to 130 °C)
ModBus port
MB1
MB2
No port
ModBus address
1–250
Table 36. Lead Lag Master Configuration
Advanced Settings: Modulation Parameters.
Parameter
Comment
Modulation backup 
sensor
Lead outlet sensor
Slave outlet sensor average
Disabled
Off hysteresis
0 °F to 234 °F
(-17 °C to 112 °C)
On hysteresis
0 °F to 234 °F
(-17 °C to 112 °C)
Hysteresis step time ___Hour ____Minute _____Second
P gain
0 - 400
I gain
0 - 400
D gain
0 - 400