TABLE 9.6: PIPE AND CIRCULATOR SIZING FOR INDIRECT WATER HEATER LOOP
BOILER 
MODEL
(a)
(b)
(c)
(d)
(e)
(f)
PIPE 
SIZE
FLOW
MAX. I.W.H. 
PRESSURE 
DROP
CROWN INDI-
RECT WATER 
HEATERS
CIRCULATOR 
MODEL
I.W.H. LOOP MAX 
EQUIVALENT 
LENGTH
(in NPT)
(GPM)
(ft HEAD) 
(ft)
BWC070
1
6.0
1.7
MS-26 (*)
MS-40 (*)
MSH-40H (*)
MT040GBR (*) 
Taco 008
122
BWC090
1
8.0
3.0
MS-26
MS-40 (*)
MSH-40H 
MT040GBR  (*)
Taco 0014
78
BWC120
1
8.0
3.0
MS-26
MS-40
MSH-40H
MT040GBR 
MT050GBR
MT065GBR
MT080GBR
Taco 0014
108
BWC120
1
8.0
5.0
MSH-53H Taco 
0014 
70
BWC151
1
8.0
3.0
MS-26
MS-40
MSH-40H
MT040GBR 
MT050GBR
MT065GBR
MT080GBR
Taco 008
49
BWC151
1
8.0
5.0
MS-53
MS-53H
MSH-79(*)
Taco 0014
150
TABLE 9.6 NOTES:
1) Indirect water heaters with an asterisk (*) will not achieve their catalog rating due to inadequate boiler water flow 
and/or inadequate boiler output.
48
TABLE 9.7: FITTING EQUIVALENT LENGTHS
FITTING
PIPE SIZE
EQUIVALENT LENGTH (ft)
90 ELBOW 
1
2.75
TURN IN TEE
1
5.50
RUN OF TEE
1
1.75
SWING CHECK
1
7.00
GATE VALVE
1
0.60