Maintenance Programming Level
Programming
MS-9200UDLS   PN 52750:A    11/04/05
123
3.7.3  Program Check
Pressing 3 while viewing Maintenance Screen #1 will cause the following screen to be 
displayed:
The Program Check feature allows the programmer to view the zones which have been 
programmed to the Notification Appliance Circuits on the control panel but have not 
been programmed to Initiating Devices as well as other circuits with no input or output 
correlations.  Pressing 1 while viewing Program Check screen will cause a screen 
similar to the following to be displayed. 
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 
and 67 but no input devices have been programmed to any of these zones.  Use the up 
and down arrow keys to view all the NAC zones without input assignments for both 
NAC 1, NAC 2, NAC 3 and NAC 4.
Note:  If the NACs have been configured for Class A in the Setup option, only NAC 1 
and NAC2 will display test information.  NAC 3 and NAC 4 will display asterisks (*) 
and will not be included in the test.
Pressing 2 while viewing the Program Check screen will display a screen similar to the 
following: 
The Zone No Input screen allows the programmer to view the zones which have not 
been programmed to at least one input device (not including general alarm Zone 00). 
The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have 
been programmed to an addressable module (control module in this example) with an 
address of 001 on loop 1 but have not been programmed to any input devices.  Use the 
up and down arrow keys to view all the zones without input assignments.
    PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Maintenance Screen #1
    PROGRAMCHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONE NO OUTPUT
Program Check Screen   
   NACS NO INPUT
NAC 1
    25 31 44 55 67
   ZONES NO INPUT
05 07 09 10 11 1M001