Specifications
Product Description
MS-9200UDLS   PN 52750:A    11/04/05
15
EIA-485 (TERM) or EIA-232 (ACS) - TB8
EIA-485 Terminal Mode annunciator connections: Terminal 1 (Out +), 2 (In +), 
3 (Out -), 4 (In -)
EIA-232 PC/Printer applications connections: Terminal 1 (Transmit), 2 (Receive), 
3 (Ground)
EIA-485 (ACS) - TB9
ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-), requires ferrite bead
1.2.1  Current Availability
The following figure illustrates the maximum current that is possible for each panel 
circuit and the total current available from the FACP with optional second transformer.
Figure 1.1 Current Availability
ow
erdist9200ud.cdr
Refer to the battery calculations section for additional information.
Note: If NACs are 
configured as two Style Z 
(Class A) circuits, each 
circuit can handle 2.5 
amps maximum.
6.0 amps with optional second 
XRM-24(E) transformer.
3.0 amps max. with only 
standard transformer installed.