Power Supply Calculations
Calculating the Battery Size
166
MS-9200UDLS   PN 52750:A    11/04/05
7.4  Calculating the Battery Size
Use Table 7.4  to calculate the total Standby and Alarm load in ampere hours (AH).  
This total load determines the battery size (in AH), required to support the control panel 
under the loss of AC power.  Complete Table 7.4  as follows:
1. Enter the totals from Table 7.3 on page 165, Calculation Columns 2 and 3 where 
shown
2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below)
3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and 
Alarm ampere hours
4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size 
(in AH)
5. Write the ampere hour requirements on the Protected Premises label located 
inside the cabinet door 
7.4.1  NFPA Battery Requirements
• NFPA 72 Local and Proprietary Fire Alarm Systems require 24 hours of standby 
power followed by 5 minutes in alarm
• NFPA 72 Central, Auxiliary and Remote Station Fire Alarm Systems require 60 
hours of standby followed by 5 minutes in alarm.  Batteries installed in a system 
powered by a generator need to provide at least 4 hours of standby power
7.4.2  Selecting and Locating Batteries
Select batteries that meet or exceed the total ampere hours calculated in Table 7.4 .  The 
control panel can charge batteries in the 7 AH to 18 AH range.  The control panel 
cabinet is capable of housing batteries up to 18 AH.  Batteries larger than 18 AH require 
a UL listed external battery charger and cabinet such as the BB-26, F or other UL listed 
external battery cabinet.
Table 7.4  Total Secondary Power Requirements at 24 VDC
Secondary Standby Load
(total from Table 7.3  Calculation 
Column 3)
[                    ]
Required Standby Time
(24 or 60 hours)
X[                    ]
=               AH
Primary Alarm Load
(total from Table 7.3  Calculation 
Column 2)
[                    ]
Required Alarm Time
(for 5 min., enter 0.084,
for 10 min., enter 0.168)
X[                    ]
=               AH
Sum of Standby and Alarm Ampere Hours
=               AH
Multiply by the Derating Factor
X 1.2
Battery Size, Total Ampere Hours Required
=               AH