Programming
Master Programming Level
58
MS-9200UDLS   PN 52750:A    11/04/05
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1. The cursor is on the first letter of the Adjective field.  Press the zero key twice to 
display FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to 
recall the display ROOM_304.  The cursor automatically jumps from the first to 
the last letter of the Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to 
increment the room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 99.  Z00 (default zone) is the general alarm 
zone.  Z01 through Z99 may be selected to link software zones
3.6.2.2  Module Programming
Pressing 2, while viewing Point Program Screen #2, will allow the programmer to 
add, delete or change the programming of an addressable module.  The following 
screen will be displayed by the control panel: 
3.6.2.2.1  Add Module
Pressing 1 while viewing the Modules Screen will display the following screen 
which allows the programmer to add a new module address to programming: 
A flashing cursor will appear in the position of the first asterisk to the left.  The 
programmer keys in the three digit module address, such as 005.  
When the last digit is keyed-in, the following screen will be displayed: 
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen #2
      MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen  
     ADD MODULE
ENTER MODULE#
***
Add Module Screen #1  
     ADD MODULE
1=CONTROL
2=MONITOR
Add Module Screen #2