Programming
Master Programming Level
76
MS-9200UDLS   PN 52750:A    11/04/05
3.6.3.2  Disable
Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following: 
This screen allows the programmer to disable zones, one at a time.  A flashing 
cursor appears next to the Z, prompting the programmer to enter a two digit zone 
number (01 - 99).  When the second digit is entered, the zone will be disabled and 
the cursor will return to the original position next to the Z.  Another zone can then 
be disabled.
3.6.3.3  Zone 97, 98 and 99
Pressing 3 for Zone 97, 98 and 99, while viewing Zone Setup Screen #1, will 
display the following screen: 
Zones 97, 98 and 99 can be programmed for normal zone operation or for special 
purpose applications.  In the above illustration, the three zones are shown Off, 
which means they can be programmed to function in the same manner as all other 
zones, by assigning them to input and output devices in the Programming Zone 
Assignment Screen.
Pressing 1 will cause the display to change to PAS 97 On.  Each press of the 1 key 
will cause the display to toggle between PAS 97 On and PAS 97 Off.  When Zone 97 
is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke 
detector will cause Zone 97 to activate.  By assigning Zone 97 to a control module 
in the Programming Zone Assignment Screen, an output device connected to the 
control module can be used to indicate a PAS condition in the control panel.  Do not 
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate 
a PAS condition.  Attempting to do so will generate an error message and will be 
prevented by software checks.
Pressing 2 will cause the display to change to Pre-signal 98 On.  Each press of the 2 
key will cause the display to toggle between Pre-signal 98 On and Pre-signal 98 
Off
.  When Zone 98 is programmed On, a Pre-signal activation of any device will 
cause Zone 98 to activate.  By assigning Zone 98 to a control module in the 
Programming Zone Assignment Screen, an output device connected to the control 
module can be used to indicate a Pre-signal condition in the control panel.  Do not 
assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate 
a Pre-signal condition.  Attempting to do so will generate an error message and will 
be prevented by software checks.
Pressing 3 will cause the display to change to Two Stage 99 On.  Each press of the 3 
key will cause the display to toggle between Two Stage 99 On and Two Stage 99 Off.  
Refer to  "Two Stage Operation" on page 90 for a description of this feature.
    ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
  ZONE TO DISABLE
Z
Disable Screen  
 SPEC PURPOSE ZONE
1=PAS 97        OFF
2=PRESIGNAL 98  OFF
3=TWO STAGE 99   OFF
Zone 97, 98 and 99 Screen