Master Programming Level
Programming
MS-9200UDLS   PN 52750:A    11/04/05
93
3.6.5.7  Canadian Option
Pressing 1 while viewing System Setup Screen #3 will allow the programmer to 
configure the system to automatically monitor addressable ionization smoke 
detector sensitivity using Canadian specifications.  The display will change to 
Canadian Opt. On.  Each press of the 1 key will cause the display to toggle between 
Canadian Opt. On and Canadian Opt. Off.:
3.6.5.8  Waterflow Silenceable
Pressing 2 while viewing System Setup Screen #3 will allow the programmer to 
configure the system for silenceable on nonsilenceable waterflow circuits.  Each 
press of the 2 key will toggle the display between Waterflow Sil. No and Waterflow 
Sil. Yes
.   When Waterflow Sil. No is selected, all output devices associated with a 
waterflow type input device, will be nonsilenceable.  When Waterflow Sil. Yes is 
selected, all output devices associated with a waterflow type input device, will be 
silenceable.
3.6.6  Verify Loop
Pressing 3 while viewing Programming Screen #2, will select the Verify Loop option. 
During loop verification, the FACP polls each device on the SLC to determine if the 
device is communicating and whether or not it responds with the proper type 
identification. The following screen will be displayed while verification is in progress:
When Loop verification has been completed, the display will indicate that the system is 
OK or, if problems have been detected, any device type programming errors.  Use the 
up and down arrow keys to view all detected errors.
   SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
     SYSTEM SETUP
1=CANADIAN OPT.  OFF
2=WATERFLOW SIL.  NO
Relays Selection Screen  
    PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
Programming Screen #2
  VERIFYING LOOPS
    PLEASE WAIT
Verification Progress Screen