Programming
Maintenance Programming Level
126
MS-9200UDLS   PN 52750:A    11/04/05
3.7.6  Zone Setup
Pressing 3 while viewing Maintenance Screen #2 will display the following screen: 
Pressing 1 while viewing Zone Setup screen will display the following screen: 
A flashing cursor appears to the right of the Z.  To enable a zone, enter the two digit 
zone number (00 - 99).  After the second digit is entered, the zone will be enabled and 
the cursor will return to the original position.  The next zone to be enabled can then be 
entered.  Press Esc (Escape) to return to the previous screen.
Pressing 2 while viewing Zone Setup screen will display the following screen: 
A flashing cursor appears to the right of the Z.  To disable a zone, enter the two digit 
zone number (00 - 99).  After the second digit is entered, the zone will be disabled and 
the cursor will return to the original position.  The next zone to be disabled can then be 
entered.  Press Esc (Escape) to return to the previous screen.
    PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
    ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen   
  ZONE TO ENABLE
Z
Enable Screen   
  ZONE TO DISABLE
Z
Disable Screen