4.2  LED Indicators
The nine LED indicators, which are located on the front panel, operate as follows:
AC Power
This is a green LED which illuminates if AC power is applied to the FACP.  A loss of 
AC power will turn off this LED
Fire Alarm
This red LED flashes when one or more alarms occur.  It illuminates steady when the 
Acknowledge/Step or Alarm Silence key is pressed.  The Fire Alarm LED turns off 
when the Reset key is pressed.  The LED will remain off if all alarms have been cleared.
Supervisory
This is a yellow LED that flashes when one or more supervisory conditions occur, such 
as a sprinkler valve tamper condition.  It illuminates steady when the Acknowledge/Step 
or Alarm Silence key is pressed.  It turns off when the Reset key is pressed and remains 
off if all supervisory alarms have been cleared.
Trouble
This is a yellow LED that flashes when one or more trouble conditions occur.  It stays 
on steady when the Acknowledge/Step or Alarm Silence key is pressed.  The LED turns 
off when all trouble conditions are cleared.  This LED will also illuminate if the 
microprocessor watchdog circuit is activated.
Maintenance
This is a yellow LED that flashes to indicate that a smoke detector requires cleaning or 
replacement due to an invalid chamber reading or excessive drift.
Alarm Silenced
This is a yellow LED that turns on after the Alarm Silence key is pressed while an alarm 
condition exists.  It turns off when the Drill or Reset key is pressed.
Disabled
This is a yellow LED that flashes to indicate that a zone, NAC, detector or module has 
been temporarily disabled in programming by the user.
Battery
This is a yellow LED that flashes to indicate a low battery voltage condition.
Ground
This is a yellow LED that flashes to indicate a ground fault condition (zero impedance 
from the FACP to ground).
Primary Line Active
This is a red LED that indicates the primary phone line is active.
Secondary Line Active
This is a red LED that indicates the secondary phone line is active
Kiss-off 
This is a green LED that blinks when a Central Station has acknowledged receipt of 
each transmitted message or when a portion of upload or download data has been 
accepted from a Service Terminal