Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Positive Alarm Sequence
Operating Instructions
MS-9200UDLS   PN 52750:A    11/04/05
137
4.19  Positive Alarm Sequence
PAS (Positive Alarm Sequence) option will program a smoke detector to delay panel 
activation (including alarm relay and communicator) for a period of 15 seconds.  Zone 
97, however, will activate immediately and may be used to connect a signaling device 
to indicate PAS activation.  Do not assign Zone 97 to a Notification Appliance Circuit 
when using this zone to indicate a PAS condition.
When a detector triggers an alarm, the onboard piezo sounds immediately, but the 
NACs are prevented from activating for 15 seconds.  This inhibit time is factory set and 
cannot be changed.  Pressing the Alarm Silence or Acknowledge/Step key during the 15 
second inhibit time will silence the piezo sounder and start a timer which prevents 
activation of NACs for an additional time duration which can be user programmed for 
up to three minutes.  After the programmed delay, the NACs will activate if the source 
of the alarm is not cleared.  Note that if a second alarm occurs during either time delay, 
the alarm will be processed immediately, causing activation of the appropriate output 
zones.  The events which occur upon PAS activation are as follows:
onboard piezo sounds immediately
control panel LCD display will indicate a presignal event and the active point
control points programmed to Zone 97 will activate
annunciators (if enabled) will sound the local piezo, and pulse the alarm LED 
and zone LED
outputs (NACs and control modules) of associated zones will be inhibited 
from activating for a factory set duration of 15 seconds
pressing the Alarm Silence or Acknowledge/Step key will start a timer which 
inhibits output activation for additional time delay of up to three minutes 
which is user programmable
second alarm occurring anytime during either time delay will cause immediate 
activation of all associated outputs
PAS operation requires the approval of the local Authority Having Jurisdiction.
Note that the PAS BYPASS monitor type code, when activated, will inhibit the PAS 
capability until the PAS BYPASS monitor is deactivated.  While PAS is inhibited, 
signaling devices will immediately place the control panel into alarm.  This feature may 
be employed by wiring a normally open device, such as a switch, to a monitor module 
which has been  programmed for PAS BYPASS.