Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Installation
Remote Synchronization Output
34
MS-9200UDLS   PN 52750:A    11/04/05
2.5.3  Style Z (Class A) NAC Wiring 
2.6  Remote Synchronization Output
Synchronization is a feature that controls the activation of notification appliances in 
such a way that all devices will turn on and off at exactly the same time.  This is 
particularly critical when activating strobes which must be synchronized to avoid 
random activation and a potential hazard to individuals.  Devices connected directly to 
the control panel’s NACs can be synchronized as described in  "Type" on page 88.
Notification appliances connected to remote power sources may require 
synchronization with the FACP’s devices.  This can be accomplished by connecting the 
Remote Synchronization Output from TB2 of the MS-9200UDLS to a compatible sync 
input of a power supply such as the FCPS-24FS6/8.  The 24 VDC, 40 mA signal from 
TB2 follows, that is mimics, the signal on NAC1.  This allows the devices connected to 
the power supply to be synchronized with the devices connected to NAC1 on the FACP.
The Remote Synchronization Output is power-limited and supervised and requires a 
ferrite bead (refer to  "UL Power-limited Wiring Requirements" on page 35).  A 4.7 k
Ω 
ELR resistor must be connected to the end of the wiring at the remote power supply.
B
+
B
+
B
-
B
-
A
+
A
+
A
-
A
-
+
+
+
+
+
+
2 Style Z (Class A) Notification Appliance Circuits, 
supervised and power-limited
Polarized Bell
Polarized Horn
Polarized Horn
Notification Appliance Circuit 
polarity shown in alarm state
Polarized Bell
Polarized Strobe
Polarized Strobe
Figure 2.9 NAC Style Z (Class A) Wiring
9200nac
z.c
dr
NAC 1
NAC 2
TB3
TB4
+ 24V - 
NON-RST
POWER
+ 24V - 
RST
POWER
REMOTE PWR
SUPPLY SYNC
+  -
B+  A+  A-  B-
B+  A+  A-  B-
1B+  3B+  3B-  1B-
2B+  4B+  4B-  2B-
TB1
TB2
TB3
TB4
JP4
1
2
3
Figure 2.10 Remote Sync Output
Remote Power Supply
FACP main circuit board
Remote Sync Output
Sync Input
4.7 k
Ω ELR