Programming
Master Programming Level
74
MS-9200UDLS   PN 52750:A    11/04/05
Description
The Description selection allows the programmer to enter additional information 
about the control module currently being programmed.  This information will be 
displayed as part of the device label on the display.  Pressing 2 while viewing Edit 
Control Screen #4 will cause the following screen to be displayed: 
A flashing cursor will appear at the first asterisk to the left.  The programmer can 
enter additional descriptive information about the device being programmed.  This 
information will appear on the display along with the standard device label 
information.  
A maximum of 20 characters (including spaces) can be entered.  To enter 
alphanumeric characters from the keypad, repeatedly press the appropriate key until 
the desired character is displayed in the first position.  For example, to enter the 
letter B, press the 2 (ABC) key three times to toggle through the characters 1A and 
B.  Press the right arrow key to move the cursor one position to the right and repeat 
the process to enter the next character.  To enter a space, press the * (QZ) key four 
times until a blank appears in the desired position.  When all characters have been 
entered, press the Enter key to store the information.  The display will return to the 
Edit Control Screen #4, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the 
cursor is on the first letter of the Adjective or Noun field as follows:
• If the zero key is pressed, a 0 is placed in the first letter position
• If the zero key is then pressed a second time with no intervening key actions, the 
entire Adjective field is replaced with the field entered for the previous device 
programmed, and the cursor moves to the last character of the field (Recall 
function).  The Recalled Adjective or Noun field may now be changed letter-by-
letter
• If the zero key is pressed again with no other intervening key actions and the last 
character in the field is a number 0-9, the number is incremented by one.  If the 
last character is a letter, it changes to a 0.  If the last character goes from 9 to 0 
and the characters to the left of the last character are also numbers, they are also 
incremented (overflow)
• The above increment function may be repeated with each press of the zero key
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1. The cursor is on the first letter of the Adjective field.  Press the zero key twice to 
display FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to 
recall the display ROOM_304.  The cursor automatically jumps from the first to 
the last letter of the Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to 
increment the room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 99.  Z00 (default zone) is the general alarm 
zone.  Z01 through Z99 may be selected to link software zones
EDIT CONTROL
1=ADJECTIVE/NOUN
2=DESCRIPTION
Edit Control Screen #4
DESCRIPTION    1M002
1=NOUN/ADJECTIVE
********************
Adjective/Noun Screen