Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Master Programming Level
Programming
MS-9200UDLS   PN 52750:A    11/04/05
79
3.6.3.8  Zones Available
Pressing 2 while viewing Zone Setup Screen #3 will display a screen similar to the 
following: 
The display will show all of the zones that are still available for programming.  Note 
that an up and/or down arrow may appear in the upper right corner of the display, 
indicating that additional screens of zone information exists.  Press the up or down 
arrow key to view additional screens.
3.6.4  Loop Setup
Loop Setup allows the programmer to configure the SLC Loop for NFPA Style 4, 6 or 7 
wiring and to select the loop protocol.  Pressing 1 while viewing Programming Screen 
#2 will cause the following screen to be displayed:
3.6.4.1  Style
To program the SLC Style for the selected loop, press 1 for Style, while viewing 
Loop Setup Screen.  In the preceding example, the control panel is programmed for 
Style 4 SLC wiring as indicated by the 4 to the right of Style in the display.  To 
change the wiring style, press 1 to toggle the display to read Style 6.  Each press of 
the 1 key will cause the display to toggle between Style 4 and Style 6.  Note that, 
when programming the Loop Style, the programmer can only select between Style 4 
and Style 6.  To program a system for Style 7 wiring, the programmer must select the 
Loop Setup for Style 6.  Style 7 wiring is the same as Style 6 with the added 
requirement that each addressable device on the loop must have a pair of isolator 
modules, one on each side.
Note on SLC Troubles:  If the FACP reports an open fault on an SLC Loop 
programmed for Style 6, the trouble condition will latch at the FACP.  When the 
SLC Loop has been repaired, the Reset button must be pressed at the FACP (at least 
2 minutes after the trouble has been repaired) to clear the SLC trouble.
3.6.4.2  Loop Protocol
Loop Protocol refers to the SLC loop mode of operation.  The two Loop Protocols 
available are CLIP (Classic Loop Interface Protocol) which is used for the older 
legacy addressable devices such as the M300 Series modules and detectors and 
LiteSpeed (factory default setting) which is used for the 350 Series or newer 
addressable devices for quicker response times.  Note that the legacy devices can 
operate only in CLIP mode while the newer devices are compatible with CLIP and 
LiteSpeed modes of operation.  Pressing 2 while viewing the Loop Setup Screen 
will toggle between CLIP and LiteSpeed Protocols. 
Device Addressing
It is important to note that the MS-9200UDLS addressable device capacity is 99 
    ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
  ZONES AVAILABLE
01 02 03 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19 20 21
    PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
Programming Screen #2
     LOOP SETUP
1=STYLE             4
2=PROTOCOL  LITESPEED
Loop Setup Screen