Programming
Master Programming Level
92
MS-9200UDLS   PN 52750:A    11/04/05
3.6.5.6  Relays
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to 
configure two of the three main circuit board Form-C relays.  The following screen 
will be displayed:
To program Relay 1 or Relay 3, press the number corresponding to the selected 
relay.  Note that Relay 2 is fixed as a Trouble relay.  Selecting Relay 2 will have no 
effect on its programming.  The following screen will appear for each relay to be 
programmed:
Pressing 1 for Type while viewing the Relay Screen will cause the following 
screens to be displayed:
While viewing the selected screen, press the number corresponding to the desired 
relay type to program the main circuit board relay.  The choice will be stored in 
memory and the display will return to the Relay Type Screen which will show the 
programmed type choice.  Press the Escape key to return to the Relays Selection 
Screen and repeat the preceding procedure for the remaining relays.
Note: AR in SUPERVISORY AR and PROCMON AR indicates AutoResettable 
which means that the relay will not latch when either of these conditions occur.  If 
the corresponding condition is cleared, the relay will return to its normal state 
without the necessity of resetting the control panel.
   SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
     RELAYS
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen  
     RELAY #
1=TYPE
              ALARM
Relay Type Screen  
     RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen  #1  
     RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS-MON
Relay Screen #2  
     RELAY
1=PROCMON AR
2=AC LOSS
3=HAZARD
Relay Screen  #3  
     RELAY
1=MEDICAL
Relay Screen #4