Operation
Operating Instructions
MS-2/MS-4   PN 51512:E  01/18/05
41
Zone Supervisory LED
A yellow LED for each zone that blinks if the zone has been programmed for 
supervisory and a supervisory condition exists on the corresponding zone.  It turns on 
steady when the Acknowledge or Alarm Silence button is pressed.
Note that an I
3
 smoke detector freeze condition is displayed as a supervisory condition.  
The zone does not have to be programmed as a supervisory for this to occur.
Zone Trouble LED
A yellow LED for each zone that blinks to indicate that a trouble exists on the 
corresponding zone.  It turns on steady when the Acknowledge or Alarm Silence button 
is pressed.
Zone Maintenance LED
A yellow LED for each zone that blinks to indicate that a I
3
 smoke detector on the 
corresponding zone is dirty or in need of maintenance.  It turns on steady when the 
Acknowledge or Alarm Silence button is pressed.
Earth Fault LED (on main circuit board)
A yellow LED that blinks to indicate a ground fault condition on the system.  A ground 
fault occurs when zero impedance between the FACP and earth ground exists.  The 
LED turns on steady when the Acknowledge or Alarm Silence button is pressed.
Battery Fault LED (on main circuit board)
A yellow LED that blinks to indicate a low battery or no battery condition on the FACP.  
It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Charger Fault LED (on main circuit board)
A yellow LED that blinks to indicate a battery charger fault.  It turns on steady when 
the Acknowledge or Alarm Silence button is pressed.
4.4  Operation
Normal mode is the standard mode of operation.  In this mode, the panel continuously 
monitors system status.  When no alarm or trouble conditions exist, the control panel 
will be in the following state:
• all LEDs will be off (except the AC Power LED)
• the Notification Appliance Circuits will be off
• all relays are in their normal state
• the onboard piezo sounder will be off
• I3 smoke detectors will be polled for maintenance and freeze conditions on initial 
entry into Normal mode.  Thereafter, each device will be polled every hour for 
freeze and every four hours for maintenance conditions
All alarm and system trouble conditions are annunciated on the control panel’s LEDs.  
Note:  To ensure that the system is functioning properly, the FACP will perform a freeze 
check five minutes after the panel is reset, followed by a maintenance check.  If there is 
no freeze or maintenance condition, the panel will continue to monitor for freeze 
conditions every hour and maintenance conditions every four hours.