MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
15
Specifications
Product Description
Auto-program (learn mode) reduces installation time.  Reports two devices set to the same 
address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or keyboard or local PC
Compatible with Fire•Lite’s newer series addressable devices (LiteSpeed and CLIP Mode) - 
Refer to SLC Wiring Manual for listing of all compatible addressable devices
Compatible with legacy Fire•Lite’s 300 Series devices (CLIP Mode only) - Refer to SLC 
Wiring Manual for listing of all compatible addressable devices
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
Optional DACT-UD2 Digital Alarm Communicator Transmitter, reports up to 99 zones or 636 
points (all devices) to a UL listed Central Station.  The DACT-UD2 is supplied standard with 
the MS-9600UDLS/E
Optional PK-CD (contains PS-Tools utility) for local or remote Upload/Download of program 
and data.
Optional DP-9692 dress panel (required for Canadian applications)
1.3  Specifications
AC Power - TB1 of Power Supply Board
MS-9600LS(C) & MS-9600UDLS: 120 VAC, 50/60 Hz, 3.0 amps (L1=Hot, L2=Neutral)
MS-9600LSE & MS-9600UDLSE: 240 VAC, 50 Hz, 1.5 amps (L1=Hot Leg 1, L2=Hot Leg 2)
Wire size: minimum 14 AWG (2.00 mm
2
) with 600 V insulation
Battery (Sealed Lead Acid Only) - TB2
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp
Maximum Battery Size: 26 Amp Hour 
Minimum Battery Size: 12 Amp Hour
(FACP cabinet holds maximum of two 18 Amp Hour batteries.  For greater than 18 Amp Hour up 
to 26 Amp Hour batteries, use BB26 Battery Box)
For greater than 26 Amp Hour up to 75 Amp Hour batteries, use the CHG-75 Battery Charger and 
BB26 or BB-55F Battery Box.  For greater than 75 Amp Hour up to 120 Amp Hour batteries, use 
the CHG-120F Battery Charger and BB-55F Battery Box.  
Jumper JP3, on the FACP main circuit board, must be removed to disable the FACP battery char-
ger when using the CHG-75 or CHG-120F.
Communication Loop - (Standard ) TB8 and (Optional SLC Expander Module) J3
24 VDC nominal, 27.6 VDC maximum
Maximum length - refer to “Wire Requirements” on page 196
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited
Refer to SLC Wiring Manual for wiring information
Notification Appliance Circuits - TB4
Special Application power
Power-limited circuitry, supervised
NAC wiring requirements, refer to “NAC Wiring” on page 197
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
NOTE: When installing SLC wiring in conduit, each loop must be installed in separate conduit.