NFPA Standard-Specific Requirements
MBT-1 Municipal Box Trip - Silenceable
C.2  MBT-1 Municipal Box Trip - Silenceable
The following figure illustrates the connection of the MBT-1 (Municipal Box Trip) between the 
FACP and a Local Energy Municipal Box.  The use of an addressable control module programmed 
for General Alarm and Silenceable allows silencing of the Municipal Box without resetting the 
panel or box. 
FACP
CMF-300
24 VDC, Nonresettable
+    -
SLC Loop B+     -B
Shield
red
black
MBT-1
brown wire
white wire
EOLR-1 Power 
Supervision Relay
Alarm polarity shown!
-
+
- To next device
+ on SLC Loop
Braided-shield/Drain Wire
The CMF-300 must be 
programmed as Silenceable 
and General Alarm.
Gamewell Model 
M34-56 Local Energy 
Municipal Box
Note:  10
 maximum loop 
resistance due to wiring from 
power supply to Municipal Box.
Connect wires to two 
red terminals on box.
(All contacts shown in energized position)