MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Installation
Power-limited Wiring Requirements
2.5  Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet.  All 
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-lim-
ited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through dif-
ferent knockouts and/or conduits.  A typical wiring diagram for the FACP is shown below.
Figure 2.9  Typical Power-limited Wiring Requirements
Power-lim
ited Circu
its
(Class 2)
Power-lim
ited Circu
its
(Class 2)
Nonpow
er-limited
 
Circuits
Power-lim
ited
Circuits
(Class 2)