Lightolier MD4GPSVA2SB4SB Manual Do Utilizador

Página de 4
AMBIENT LIGHT
Ambient Light
Indirect illumination from wall directly behind patient provides glare-free lighting..
No direct glare to patient. (Light is directed towards wall.)
No direct glare to patient's visitor.
No direct glare to adjacent patients. (3 footcandles maximum on wall behind adjacent patients bed.)
Reading Light
Eliminates reflected glare from reading material (over shoulder illumination).
No direct glare to patient or visitors. (7 footcandles maximum at head of bed. 15 footcandles maximum at foot of bed.)
Controls light directly onto patient's bed.
No reading light spill-over to adjacent bed (2 foot/candles maximum at head of adjacent patient's bed.)
FOOTCANDLES ON BED (with Specular Louver)
Totals of ambient, reading and examination lights.
Examination Light
Excellent color rendition. (Biax Type lamp.)
Wired for independent switching (1 or 2 circuit).
Optional louver or lens frame.
Concealed hinging and latching.
Numbers in parenthesis (  ) are total footcandle
level of ambient and reading lights only.
70
82
82
102
100
70
48
(11)
(12)
(15)
(45)
(43)
(20
(10)
75
82
86
107
102
72
48
(11)
(12)
(15)
(45)
(43)
(20)
(10)
70
82
82
102
100
70
48
(11)
(12)
(15)
(45)
(43)
(20)
(10)
ADJACENT
MD*4
ON
MD*4
TM
2' x 4' Recessed or Surface 
MD4GPSVA2SB4SB
Page 2 of 4
Multi-Function Patient Lighting
LIGHTED
ZONE
SHIELDED
ZONE
LIGHTED
ZONE
3"
←6"
← 12"
BED
12"
SHIELDED
ZONE
45
110
140
110
45
14
4
2
1
1
1
1
44
83
95
83
44
19
7
3
2
2
1
1
30
45
50
45
30
16
8
4
3
3
2
1
16
20
22
20
16
11
7
4
3
3
2
1
7
9
9
7
4
3
2
2
1
1
3
3
2
2
1
1
1
2
1
1
OFF
Illumination at the reading task range 50-60 footcandles
READING LIGHT
ON
ADJACENT
MD*4
OFF
FOOTCANDLES ON BEDS
WALL
3"
6"
BED
BED
12"
↓3"
6"
12"

2
2
2
2
2
2
1
1
1
1
1
1
3
3
3
3
3
2
2
2
1
1
1
1
6
7
7
7
6
4
3
3
2
2
1
1
33
38
39
38
33
23
16
12
9
5
3
2
30
38
38
38
30
23
15
12
8
6
3
2
14
15
15
15
14
11
9
7
5
4
2
2
5
5
5
5
5
5
4
4
2
2
1
1
Illumination at the
reading task ranges
50-60 footcandles.
LIGHTED
ZONE