LST UVIR2 16591 Folheto

Página de 2
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
UVIR2-16591_DBL_LST_EN_0850.PDF • PAGE 1
A
Building Safety. Building Security.
Description
•   UV sensor combined with dual IR 
sensor, according to EN 54-10,
Class 1
•   Detection of open fl ames through 
fl ickering IR and UV radiation
•   Highest immunity to deceptive alarms
•  Selectable response delay
•   Relay contacts for alarm and fault
•  Integrated optical test function
The Flame Detector 16591 responds to the fl ickering 
infrared and ultraviolet radiation of open fl ames. There-
fore, it is extremely well suitable for the detection of 
fi res which are diffi cult to detect with common smoke 
detectors – for example, alcoholic fi res or gas fl ames.
The detector is ideal for the following applications:
  • Aircraft hangars
  • Power stations and turbine plants
  • Military bases
  • Nuclear facilities
  • Fuel depots
Thanks to the combination of two independent infrared 
sensors for different wavelengths and an UV sensor as 
well as an intelligent evaluation logic, the detector can 
distinguish particularly safely between alarm situations 
and deceptive alarms. Therefore, it is very insensitive 
to  disturbance  sources  such  as  sunlight,  fl uorescent 
lamps or electric arcs.
The detector complies with EN 54-10, Class 1, which 
means it is suitable to detect fl ames up to a distance 
of 25m.
The response delay of the detector can be selected in 
4 steps between 1 and 8s. An alarm and a fault conditi-
on is signalled via two dry relay contacts. Conventional 
technology  is  used  for  alarm  transmission  to  the  fi re 
detection control panel. The detector can be integra-
ted into an ADM loop by means of a conventional zone 
module.
A  simple  test  of  the  detector  can  be  carried  out  by 
means of the integrated optical self test function, which 
does not require additional tools. During this self test, 
built-in infrared and ultraviolet light sources simulate a 
fi re situation which activates the detector.
The detector has been designed for indoor and outdoor 
use. The optional Detector Mounting Bracket 7127 al-
lows stepless horizontal and vertical adjustment for the 
easy adaptation of the detector to the required monito-
ring area.
For use in explosion-hazardous areas, an Ex version of 
the fl ame detector is available on request.