LST M220E Folheto

Página de 2
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
M220E_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The  addressable  Monitor  Module  M220E  serves  for 
the line-monitored integration of two contact detectors, 
such as manual call points, sprinkler system contacts 
or supervising contacts, into the bidirectional commu-
nication  on  the  ADM  loop  with  System  Sensor/200 
protocol. 
Each  input  has  an  individual  status  LED.  Separate 
terminals enable the operation of the module with or 
without the integrated dual-isolator.
Accessories for mounting on a wall, on a plate or on a 
DIN rail are available.
•   ADM loop technology with 
System Sensor/200 protocol
•   Two inputs with lines monitored for 
wire breakage and short circuit
•   Status LEDs
•   Setting of module address via 
decadic rotary switches
•   Mounting in module box or by means 
of mounting base
Specifi cations
Operating voltage 
Supply through loop voltage
Current consumption 
approx. 600µA (quiescent)
Ambient temperature 
-20°C to +60°C
Dimensions L × W × H 
93 × 94 × 23 (mm)
Colour 
cream
Weight 
110g
Approval 
VdS G202140
Order number 
249101
Order name 
Monitor Module 2xSurv.In/Anal./200/SS M220E