Building Safety. Building Security.
Description
The  addressable  Module  M221E  serves  for  the  line-
monitored integration of 2 contact detectors, such as 
manual call points, sprinkler system contacts or super-
vising  contacts,  into  the  bidirectional  communication 
on the ADM loop with System Sensor/200 protocol. 
Furthermore,  it  can  be  used  to  actuate  external  de-
vices by means of a relay output with a dry change-
over contact, via the ADM loop. Each input as well as 
the output have individual status LEDs. Separate termi-
nals enable the operation of the module with or without 
the integrated dual-isolator.
Accessories for mounting on a wall, on a plate or on a 
DIN rail are available.
•   ADM loop technology with 
System Sensor/200 protocol
•   Two input lines monitored for wire 
breakage and short circuit 
•  One dry relay output
•   Setting of module address via 
decadic rotary switches
•   Mounting in module box or by means 
of mounting base
Specifi cations
Operating voltage 
Supply through loop voltage
Current consumption 
approx. 660µA (quiescent)
Contact rating 
2A/30VDC or 0.5A/125VAC
Ambient temperature 
-20°C to +60°C
Dimensions L × W × H 
93 × 94 × 23 (mm)
Colour 
cream
Weight 
110g
Approval 
VdS G202139
Order number 
249102
Order name 
Module 2xSurv.In 1xRel.Out/Anal./200/SS M221E