LST 55100-908 Folheto

Página de 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
55100-908_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Specifi cations
Description
The  Manual  Call  Point  55100-908  complies  with  the 
standard EN 54-11/A and is designed for use in ADM 
loops with Apollo/Discovery protocol.
The  detector  is  activated  by  pressing  in  the  pane  of 
plastic.  By  means  of  a  special  key,  the  pane  can  be 
put back to the idle position, thereby resetting the de-
tector.
The two-coloured status LED indicates the activation of 
the detector in red colour and the fault condition in yel-
low colour. The detector address is selected by means 
of a DIL switch. A dual-isolator, which is integrated into 
the detector, disconnects the adjacent loop elements 
fast and safely in case of a short circuit.
The  detector  is  fi tted  into  a  plastic  case  and  can  be 
mounted  on  a  60mm  fl ush-mount  installation  box.  By 
means of the supplied case, surface mounting on a wall 
is also possible.
•   ADM loop technology with
Apollo/Discovery protocol
•   Activation by pressing in the pane of 
plastic
•   Two-coloured LED indicates activation 
and fault
•  Integrated dual-isolator
•   Operating instructions by means of 
standardised symbols
Operating voltage 
Supply through loop voltage
Current consumption 
100µA (quiescent)
Ambient temperature 
-20°C to +60°C (no condensation or icing)
Relative humidity 
max. 95% (no condenstation)
Protection class 
IP24
Dimensions W × H × D
   with surface mount box 
89 × 93 × 59 (mm)
   installation on fl ush-mount installation box 
89 × 93 × 28 (mm)
Colour 
fl ame red, RAL 3000
Weight 
160g
Order number 
245015
Order name 
Manual Call Point/Red/XP95/ISM/Flexi 55100-908