iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide 
 
– 1 – 
General Information 
The iPGSM-COM Commercial Fire Communicator includes everything you need to upgrade a commercial 
fire system that previously reported by POTS to a system that uses the Internet as its primary reporting 
path, and uses a GSM cellular reporting path as a backup.  In addition, this communicator utilizes a 
sophisticated power module (PowerBoost1) that monitors and reports AC power loss, low battery, and 
missing battery conditions.  
Package Contents 
 
Red Fire Cabinet and Back Plate 
 
50 ohm cable assembly  
 
Transformer, 18VAC (N8167) 
 
Cam Lock with Key 
 
Antenna and Mounting Adapter 
 
Ferrite Filter 
 
Dialer Capture Module 
 
PowerBoost1 
 
Hardware Bag 
 
LED Display board 
 
Battery harness 
 
 
iGSM Communications Module 
 
Wall Outlet Box (P/N K14358) 
 
 
Compatible Fire Panels 
The iPGSM-COM works with Fire Panels that use the Contact ID communication format as described in the 
SIA DC-05 Standard.  After completing the field installation, verify communications with the central station 
is successful by sending several events.  Also, get confirmation that these events were received.  
Note: For a fire panel that has more than 9 active partitions, the first 9 partitions are reported to the 
central station uniquely.  Beyond 9 partitions, only the 2nd digit of the partition is reported along with 
a leading zero (example partition 14 is reported as 04).  The installer must inform the central 
station of this condition.  
Operation 
The iPGSM-COM replaces the fire panel's POTS communications path.  When an event occurs, the fire panel 
goes off-hook to dial the central station.  The iPGSM-COM detects the off-hook condition and provides the 
fire panel with a dial tone.  When the fire panel detects the dial tone, it begins dialing the central station.  
The iPGSM-COM considers the three second period after dialing as the number dialing has been completed.  
After the dialing is completed, the Dialer Capture Module returns a handshake to the fire panel. 
The fire panel then sends the contact ID reports to the iPGSM-COM, which in turn sends a kiss-off after the 
report is successfully received from the fire panel.  Within the iPGSM-COM, the Dialer Capture Module  
sends the contact ID reports over the ECP bus to the iGSM Communications Module.  When all the reports 
are sent, the fire panel goes on-hook.  The iPGSM-COM then transmits the messages to the central station 
(either over the internet or the GSM network).  
Installation 
UL Compliance 
To meet UL864/NFPA, ensure the following:   
 
Equipment should be installed in accordance with NFPA (National Fire Protection Association) 
standards 70 and 72. 
 
iPGSM-COM must be mounted in the same room and within 20 feet of the fire panel.     
 
iPGSM-COM, and all equipment used for the IP connection (such as the router, hub, modem, etc.) 
must be powered from the same un-switched facility power source branch as the fire panel.   
 
iPGSM-COM must use a 7AH battery (not supplied) to provide 24-hour backup capability.