Section 7
Programming
This section of the manual describes how to manually program the control panel from the 
built-in annunciator. Each subsection discusses these menu options in detail. All options 
described in this section can be performed using the 5660 Silent Knight Software Suite 
(SKSS).
7.1
UL 864 Programming Requirements
Important!
Before any customized programming is done, JumpStart should be run first. After 
JumpStart is run, thoroughly test the system. The reason the system should be tested 
after JumpStart is because Jumpstart automatically programs the system, searching for 
and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm 
the integrity of the installation prior to performing any custom programming. After 
determining that the hardware is properly installed, custom programming can be 
performed. Refer to Section 6.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND 
OTHER INVOLVED PARTIES: This product incorporates field programmable software. In 
order for the product to comply with the requirements in the Standard for Control Units and 
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be 
limited to specific values or not used at all as indicated below.
Programming Option
Menu Item
Permitted in
UL 864 (Y/N)
Possible 
Settings
Settings Permitted in 
UL 864
Phone Lines
Enable Gnd Start
No
Yes & No
No
Misc Options 1
Low AC Report Delay
Yes
0–30 hours
1–3