Honeywell 25/50ZS Manual Do Utilizador
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
105
Appendix D: Programmed Activation by FACP
The Audio Command Center Zone Split system (ACC-25/50ZS/T) can be automatically controlled
by any FACP. The following table lists the available audio features and the control signals that are
required from the FACP.
by any FACP. The following table lists the available audio features and the control signals that are
required from the FACP.
Column Descriptions for Table D.1
•
FACP - the Fire Alarm Control Panel being used
•
ACC-ZPMK S1 DIP switch Setting - the DIP switch setting on the ACC-ZPMK in accordance
with the FACP installed
with the FACP installed
•
Individual Audio Zone Control via ACS/ANN-BUS Link - ACS or ANN-BUS compatible
FACPs can control each audio zone on the ACC-25/50ZS or ACC-25/50ZST (refer to the
FACP specific programming sections in this Appendix)
FACPs can control each audio zone on the ACC-25/50ZS or ACC-25/50ZST (refer to the
FACP specific programming sections in this Appendix)
•
Individual Control of All Messages - control of all voice messages in the ACC-25/50ZS or
ACC-25/50ZST can be accomplished through the ACS/ANN-BUS link or by triggering the
CMD inputs (refer to the FACP specific programming sections in this Appendix.)
ACC-25/50ZST can be accomplished through the ACS/ANN-BUS link or by triggering the
CMD inputs (refer to the FACP specific programming sections in this Appendix.)
FACP
ACC-
ZPMK
S1 DIP
Switch
Switch
Settings
1 2 3
Individual
Audio
Zone Control
via
Serial Link
Individual Control of
All Messages
Simultaneous
Activation of All
Audio Zones
1
Fire Fighter
Telephone
Remote
Annunciation
via
Serial Link
ACS
ANN
ACS
ANN
CMD ACS
ANN
Non-ACS/ANN-BUS FACP or
MS-9200UD version 1
2
0 0 0
No
No
No
No
Yes
Yes
No
No
MS-5210UD
0 0 1
Yes
No
No
3,4
No
Yes
No
No
No
MS-9200
0 1 0
Yes
No
No
3
No
Yes
5
Yes
Yes
No
MS-9600 version 1
0 1 1
Yes
No
No
No
Yes
Yes
Yes
No
MS-9600 version 2 or 3
1 0 0
Yes
No
No
No
Yes
6
Yes
Yes
No
MS-9200UDLS or
MS-9200UD version 2 or 3
1 0 1
Yes
No
Yes
No
Yes
Yes
Yes
7
No
MS-9200UDLS version 4 or higher
1 1 0
Yes
Yes
Yes
Yes
Yes
Yes
Yes
8
Yes
MS-9600LS version 4 or higher
1 1 0
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
MS-5UD-3/7 or MS-10UD-3/7
version 2 or higher
1 1 0
No
Yes
No
Yes
Yes
9
Yes
No
No
future
1 1 1
Table D.1 FACP Message/Zone Control of the ACC-25/50ZS/T
1 There may be up to an 8 second delay between alarm indication on the FACP and activation of the message and
speaker zones on the ACC-25/50ZS/T.
2 ACS link control utilizing the MS-9200UD version 1 is not available.
3 The MS-5210UD can control up to 5 messages via the ACS link using the ACM-8RF Relay Module
3 The MS-5210UD can control up to 5 messages via the ACS link using the ACM-8RF Relay Module
.
4 Only Message #1 can be automatically activated by the FACP via ACS control.
5 Program Software Zone 32 in the FACP to activate all the Audio Zones on the ACC-25/50ZS/T.
6 For CMD Input Control using version 2 or higher, set the ACC-ZPMK DIP switch for MS-9600 version 1.
7 Enable ACS address 07 to annunciate remote FFT locations.
8 Enable ACS address 05 to annunciate remote FFT locations.
9 For CMD Input Control using the MS-5UD-3/7 or MS-10UD-3/7, set the ACC-ZPMK DIP switch for
5 Program Software Zone 32 in the FACP to activate all the Audio Zones on the ACC-25/50ZS/T.
6 For CMD Input Control using version 2 or higher, set the ACC-ZPMK DIP switch for MS-9600 version 1.
7 Enable ACS address 07 to annunciate remote FFT locations.
8 Enable ACS address 05 to annunciate remote FFT locations.
9 For CMD Input Control using the MS-5UD-3/7 or MS-10UD-3/7, set the ACC-ZPMK DIP switch for
Non-ACS/ANN-BUS FACP.