Honeywell HA40 Manual Do Utilizador

Página de 39
HA40 4-Channel Controller
Revision 1 (07/08)
HA40 Technical Manual
6-2
5 Specifications
Input power:
100-240 VAC, 50/60 Hz 
24 VDC
DC output power:
15 watts (internal supply) 
50 watts (optional external supply)
Relay output rating:
5A, 28 VDC or 250 VAC (resistive load)
Optional relay output rating
5A, 28 VDC or 250 VAC (resistive load)
Optional milliamp loop 
output
10 bit 4-20mA output. Maximum load 750 ohms 
with nominal 24 Vdc
Communication:
RS232 Modbus
Length of communication 
lines:
Operating environment:
Industrial 
Operating temperature 
range:
-25 to 50ºC (-13ºF to 122ºF)
Operating humidity range:
0 to 90% RH non-condensing
Operating altitude:
2000m (6562 ft)
Audible alarm:
100 dB
Display:
128 x 64, backlight graphic LCD
Visual Indicators:
6 LED status indicators
Pollution degree:
N4: 3
Enclosure (N4):
NEMA 4X, Div. 2, Groups A,B,C,D, Category II
Enclosure (XP):
NEMA 7, Div. 1 & 2, Groups B,C,D
Dimensions (H x W x D):
N4: 10.32” x 8.92” x 3.17” (23.62 x 22.66 x 8.05cm)
XP: 15.10” x 13” x 6.25” (36.2 x 33 x 15.88cm)
Weight:
N4: 2.27 Kg     XP: 18.14 Kg
Certifications:
CSA C22.2 No. 1010-1, ISA S82.02 
CSA C22.2 No 152 (for combustibles using mA 
input) 
UL 1604/C22.2 No. 213 (NEMA 4X = Div 2, Gr A, 
B, C, D; NEMA 7 = Div 1, Gr , B, C, D 
EN55011 & EN61000 (CE mark))